Plan Review Notes For Permit 05061718 |
Permit Number |
05061718 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2006-02-10 00:00:00 | REDLINED: | | | | | | 250.52A5 GRND ROD SHALL BE A MIN OF 8' | | | | VIF OCP FOR CU, SHOWS 9.8KW ON 40A OCP | | | | OCP FOR AHU# 2 SHALL BE SIZED PER | | 424.3B, MIN OCP TO BE 125%. |
|