Plan Review Notes
Plan Review Notes For Permit 05061718
Permit Number 05061718
Review Stop E
Sequence Number 2
Notes
Date Text
2006-02-10 00:00:00REDLINED:
  
  
 250.52A5 GRND ROD SHALL BE A MIN OF 8'
  
 VIF OCP FOR CU, SHOWS 9.8KW ON 40A OCP
  
 OCP FOR AHU# 2 SHALL BE SIZED PER
 424.3B, MIN OCP TO BE 125%.