2006-03-14 00:00:00BUILDING REVIEW CHECKLIST:
  
 1- ENERGY CALCULATIONS SUBMITTED SHOW
 THAT CREDIT IS TAKEN FOR CEILING FANS.
 REVISE ELECTRICAL PLANS AS REQUIRED TO
 SHOW CEILING FANS IN ALL ROOMS. SEE
 TABLE 6-6 OF CHAPTER 13 FBC 2001 FOR
 MINIMUM NUMBER AND SIZE OF CEILIG FANS
 REQUIRED FOR EACH ROOM. SHOW SIZE AND
 NUMBER REQUIRED IN ELECTRICAL PLAN.
  
 2- ARCHITECT SIGNED AND SEALED PRODUCT
 APPROVAL FOR ATRIUM DOOR. ARCHITECT IS
 NOT ALLOWED TO SIGN AND SEAL DOCUMENTS
 THAT HE DIDN'T DESIGNED OR PRODUCED
 UNDER HIS SUPERVISION. ARCHITECT TO SEE
 FLORIDA ADMINISTRATIVE CODE. RE-SUBMIT
 AS REQUIRED.
  
 NOTE:
 PLANS FOR THIS HOUSE WERE APPROVED UNDER
 FBC 2001, NOT FBC 2004. CITY AMENDMENTS
 TO FBC 2004 IS THE CODE THAT REQUIRES
 DESIGNER OF RECORD TO REVIEW AND APPROVE
 IN WRITTING (NOT SIGN AND SEAL) ALL
 PRODUCT APPROVALS.
  
 3- CONTRACTOR TO APPLY FOR STORM
 SHUTTERS PERMIT AS AGREED ON PROVISO AS
 SOON AS POSSIBLE TO AVOID CONFLICT OR
 DELAYS.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712.