Plan Review Notes For Permit 05061533 |
Permit Number |
05061533 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2006-03-14 00:00:00 | BUILDING REVIEW CHECKLIST: | | | | 1- ENERGY CALCULATIONS SUBMITTED SHOW | | THAT CREDIT IS TAKEN FOR CEILING FANS. | | REVISE ELECTRICAL PLANS AS REQUIRED TO | | SHOW CEILING FANS IN ALL ROOMS. SEE | | TABLE 6-6 OF CHAPTER 13 FBC 2001 FOR | | MINIMUM NUMBER AND SIZE OF CEILIG FANS | | REQUIRED FOR EACH ROOM. SHOW SIZE AND | | NUMBER REQUIRED IN ELECTRICAL PLAN. | | | | 2- ARCHITECT SIGNED AND SEALED PRODUCT | | APPROVAL FOR ATRIUM DOOR. ARCHITECT IS | | NOT ALLOWED TO SIGN AND SEAL DOCUMENTS | | THAT HE DIDN'T DESIGNED OR PRODUCED | | UNDER HIS SUPERVISION. ARCHITECT TO SEE | | FLORIDA ADMINISTRATIVE CODE. RE-SUBMIT | | AS REQUIRED. | | | | NOTE: | | PLANS FOR THIS HOUSE WERE APPROVED UNDER | | FBC 2001, NOT FBC 2004. CITY AMENDMENTS | | TO FBC 2004 IS THE CODE THAT REQUIRES | | DESIGNER OF RECORD TO REVIEW AND APPROVE | | IN WRITTING (NOT SIGN AND SEAL) ALL | | PRODUCT APPROVALS. | | | | 3- CONTRACTOR TO APPLY FOR STORM | | SHUTTERS PERMIT AS AGREED ON PROVISO AS | | SOON AS POSSIBLE TO AVOID CONFLICT OR | | DELAYS. | | | | JULIO GOMEZ | | BUILDING PLANS EXAMINER | | (561)805-6712. |
|