Plan Review Notes
Plan Review Notes For Permit 05061479
Permit Number 05061479
Review Stop E
Sequence Number 5
Notes
Date Text
2006-04-18 00:00:00********** UNSAT **********
  
 PLEASE SEE THE FOLLOWING COMMENTS AS
 PLANS ARE COMING IN WITH A COMPLETE;Y
 DIFFERENT RISER FROM PREVIOUS PLANS
 SUBMITTED.
  
  
 1) NOTE: PLEASE BE SURE SEAL FROM
 ARCHITECT IS CLEAR AND VISABLE WITH ALL
 INFORMATION ON SIAD SEAL. PLEASE SEE
 SEAL IS UNREADABLE AT THIS TIME.
 FS 481.221,FAC 61G1-16.003
  
 2) NOTE: PLEASE CORRELATE RISER WITH NEW
 PANEL "B". (MISPRINT ON RISER.
 215.5
  
 3) NOTE: PLEASE SEE A NEW PANEL IS BEING
 SHOWN FROM EXISTING PLANS WHICH NOW
 SHOWS PANELS BEING SUB-FED FROM THIS NEW
 PANEL, HOWEVER OCP CAN NOT VERIFIED AT
 THIS TIME AND NO PANEL SCHEDULE WAS
 SUBMITTED FOR THIS NEW PANEL.
 215.5
 PLEASE PROVIDE PANEL SCHEDULE AND
 INDICATE ALL NEW OCP FOR PANELS "B" AND
 PANEL "OLD EXISTING".
 PLEASE LABEL ALL PANELS.
  
 4) NOTE: PLEASE SEE "OLD" PANEL IS SHOWN
 AS 50A ON RISER AND 60A ON PANEL
 SCHEDULE?
 215.5
  
 5) NOTE: PLEASE SHOW THE LOCATION OF THE
 NEW SERVICE ON PLANS. METER/MAIN.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  