2005-09-09 00:00:00****** PROVISO/ REVISION ************
  
 1)NOTE: PLEASE SHOW THE SERVICE ENTRANCE
 CONDUCOTR AND SIZEOF RISER.
 240.4,310.15B6,310.16,215.5
  
 2)NOTE: PLEASE CORRELATE FEEDERS ON
 RISER TO EXSITNG PANEL "A" WITH FEEDERS
 SHOWN ON NEW MCB PANEL.
 PLEASE SEE ONE SHOWS #2 AND THE OTHER AS
 #1.
  
 PLEASE SUBMIT THE ABOVE ALONG WITH ANY
 OTHER REVISIONS, BEFORE ANY ROUGH
 ELECTRICAL INSPECTIONS ARE CALLED IN.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]