2005-09-09 00:00:00 | ****** PROVISO/ REVISION ************ | | | | 1)NOTE: PLEASE SHOW THE SERVICE ENTRANCE | | CONDUCOTR AND SIZEOF RISER. | | 240.4,310.15B6,310.16,215.5 | | | | 2)NOTE: PLEASE CORRELATE FEEDERS ON | | RISER TO EXSITNG PANEL "A" WITH FEEDERS | | SHOWN ON NEW MCB PANEL. | | PLEASE SEE ONE SHOWS #2 AND THE OTHER AS | | #1. | | | | PLEASE SUBMIT THE ABOVE ALONG WITH ANY | | OTHER REVISIONS, BEFORE ANY ROUGH | | ELECTRICAL INSPECTIONS ARE CALLED IN. | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|