2005-08-12 00:00:00DENIED:
 1. FL. ENERGY CAL. IS CALLING FOR 18,600
 BTU'S & 12 SEER, PLANS SHOW 36,000
 BTU'S & 11 EER TO BE INSTALLED. FL.
 ENERGY CAL. & PLANS NEED TO COINCIDE
 WITH EACH OTHER.
 2. AUXILIARY DRAIN PAN SHOULD BE PLACED
 BELOW A/H STAND AND HAVE A FLOAT SWITCH
 INSTEAD OF AN AUXILIARY DRAIN LINE.
 IF YOU HAVE ANY QUESTIONS PLEASE CALL
 TOM GORDON 805-6729 OR PATTY KRAUSS
 805-6719.
  