Date |
Text |
2005-08-09 00:00:00 | *********** UNSAT 2ND REVIEW ********* |
| |
| PLEASE SEE SOME NOTES FROM PREVIOUS |
| REVIEW STILL NEED TO BE ADDRESSED. |
| |
| 1)NOTE: PLEASE SEE ZONING COMMENTS, |
| PLEASE SEE BLDG COMMENTS IN REFERENCE TO |
| SUREVEY. SURVEY IS REQUIRED TO BE |
| SIGNED, DATED AND SEALED . MUST CONTAIN |
| ORIGINAL SIGNATURE, ALL LICENSE |
| INFORMATION FOR COMAPNY ETC. |
| FS 472.025,471.021,FAC 61G17-7.002 |
| PLEASE SEE SURVEY SUBMITTED CONTAINS A |
| RAISED SEAL OVER A PHOTOCOPIED |
| SIGNATURE. |
| |
| 2)NOTE: PLEASE SEE NOTES IN TWO |
| LOCATIONS ON PLANS MENTIONS SERVICE TO |
| BE UPGRADE "IF" REQUIRED. PLEASE SEE |
| PLANS NOW SUBMITTED INDICATE A NEW |
| SERVICE BEING INSTALLED? |
| PLEASE SHOW NEW SEC'S IN RISER AND SIZE |
| OF RISER. |
| 215.5,310.15B6,310.16, ETC. |
| |
| 3)NOTE: PLEASE SEE RISER NOW SHOWS AN |
| "EQUIPMENT GROUNDING" CONDUCTOR FROM |
| METER TO MAIN. PLEASE SEE 250.6,250.24, |
| AN "EQUIPMENT GROUNDING" CONDUCTOR IS |
| ONLY INSTALLED AFTER THE FIRST MEANS OF |
| DISCONNECT. |
| |
| 4)NOTE:PLEASE SEE FBC CHAPTER 34, |
| EXSITING HOUSE SHOWS NEW SD'S, HOWEVER, |
| PLEASE SEE ALL EXISTING LOCATION WHICH |
| REQUIE GFI UNDER THE 2002 NEED TO BE |
| SHOWN. (BATHS) ETC. |
| 210.8 |
| |
| 5)NOTE: PLEASE SEE 210.52D,210.11C3, ALL |
| BATH DEDICATED CIRCUITS ARE REQUIRED TO |
| BE 20A AND #14. PLEASE SEE #14, 15A |
| SHOWN. |
| |
| 6)NOTE: PLEASE SEE SD'S ARE STILL BEING |
| NOTED TO BE CIRCUITED TO KITCHEN AND |
| BATH LT CIRCUITS. |
| PLEASE KNOW THAT ALL SD'S ARE REQUIRED |
| TO BE WIRED "INLINE". PLEASE ALSO SEE |
| THAT UNDER THE 2002 NEC 210.12, THEY ARE |
| ALSO REQUIRED TO HAVE ARC FAULT |
| PROTECTION. ARC FAULT PROTECTION IS |
| NOTED ON PLANS, HOWEVER IF THE SD'S ARE |
| WIRED TO KIT/BATH LIGHTING CIRCUITS, |
| THIS WOULD MOST LIKLEY REQUIRED RE-WIRE |
| OF THOSE EXISTING CIRCUITS IN ORDER TO |
| PROVIDE ARC FAULT PROTECTION. |
| PLEASE CALL TO GO OVER THIS SCENERIO. |
| |
| 7)NOTE: PLEASE SEE A COPY OF FS |
| 553.80(2)(B) IS NOW ATTACHED WITH |
| RESPECT TO DESIGN PROFESSIONAL. PLEASE |
| SEE THIS IS ONLY A NOTICE GIVEN AT THIS |
| TIME. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE BE SURE TO SEE COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |