Plan Review Notes
Plan Review Notes For Permit 05061479
Permit Number 05061479
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-09 00:00:00*********** UNSAT 2ND REVIEW *********
  
 PLEASE SEE SOME NOTES FROM PREVIOUS
 REVIEW STILL NEED TO BE ADDRESSED.
  
 1)NOTE: PLEASE SEE ZONING COMMENTS,
 PLEASE SEE BLDG COMMENTS IN REFERENCE TO
 SUREVEY. SURVEY IS REQUIRED TO BE
 SIGNED, DATED AND SEALED . MUST CONTAIN
 ORIGINAL SIGNATURE, ALL LICENSE
 INFORMATION FOR COMAPNY ETC.
 FS 472.025,471.021,FAC 61G17-7.002
 PLEASE SEE SURVEY SUBMITTED CONTAINS A
 RAISED SEAL OVER A PHOTOCOPIED
 SIGNATURE.
  
 2)NOTE: PLEASE SEE NOTES IN TWO
 LOCATIONS ON PLANS MENTIONS SERVICE TO
 BE UPGRADE "IF" REQUIRED. PLEASE SEE
 PLANS NOW SUBMITTED INDICATE A NEW
 SERVICE BEING INSTALLED?
 PLEASE SHOW NEW SEC'S IN RISER AND SIZE
 OF RISER.
 215.5,310.15B6,310.16, ETC.
  
 3)NOTE: PLEASE SEE RISER NOW SHOWS AN
 "EQUIPMENT GROUNDING" CONDUCTOR FROM
 METER TO MAIN. PLEASE SEE 250.6,250.24,
 AN "EQUIPMENT GROUNDING" CONDUCTOR IS
 ONLY INSTALLED AFTER THE FIRST MEANS OF
 DISCONNECT.
  
 4)NOTE:PLEASE SEE FBC CHAPTER 34,
 EXSITING HOUSE SHOWS NEW SD'S, HOWEVER,
 PLEASE SEE ALL EXISTING LOCATION WHICH
 REQUIE GFI UNDER THE 2002 NEED TO BE
 SHOWN. (BATHS) ETC.
 210.8
  
 5)NOTE: PLEASE SEE 210.52D,210.11C3, ALL
 BATH DEDICATED CIRCUITS ARE REQUIRED TO
 BE 20A AND #14. PLEASE SEE #14, 15A
 SHOWN.
  
 6)NOTE: PLEASE SEE SD'S ARE STILL BEING
 NOTED TO BE CIRCUITED TO KITCHEN AND
 BATH LT CIRCUITS.
 PLEASE KNOW THAT ALL SD'S ARE REQUIRED
 TO BE WIRED "INLINE". PLEASE ALSO SEE
 THAT UNDER THE 2002 NEC 210.12, THEY ARE
 ALSO REQUIRED TO HAVE ARC FAULT
 PROTECTION. ARC FAULT PROTECTION IS
 NOTED ON PLANS, HOWEVER IF THE SD'S ARE
 WIRED TO KIT/BATH LIGHTING CIRCUITS,
 THIS WOULD MOST LIKLEY REQUIRED RE-WIRE
 OF THOSE EXISTING CIRCUITS IN ORDER TO
 PROVIDE ARC FAULT PROTECTION.
 PLEASE CALL TO GO OVER THIS SCENERIO.
  
 7)NOTE: PLEASE SEE A COPY OF FS
 553.80(2)(B) IS NOW ATTACHED WITH
 RESPECT TO DESIGN PROFESSIONAL. PLEASE
 SEE THIS IS ONLY A NOTICE GIVEN AT THIS
 TIME.
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE SURE TO SEE COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]