Plan Review Notes
Plan Review Notes For Permit 05061479
Permit Number 05061479
Review Stop E
Sequence Number 1
Notes
Date Text
2005-07-11 00:00:00************ UNSAT ***************
  
 1)NOTE: PELASE SEE ZONING COMMENTS
 PERTAINING TO MIN SET-BACKS REQUIRED.
 PLEASE SEE THIS WILL AFFECT ALL PLANS
 FOR ALL TRADES.
  
 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES
 AND RISER DIAGRAM.
 PLEASE SEE PANEL "B" SHOWS # 1 ON NEW
 MDP AND 1/0'S ON RISER.
 PLEASE SEE NEW PANEL "B" IS SHOWN AS
 PANEL "E" ON RISER.
 PLEASE ALSO SEE LABELING OF PANELS ON
 LOAD CALCULATIONS.
 215.5
  
 3)NOTE: PLEASE SEE PLANS ARE NOTED TO
 MENTION "UPGRADE EXISTING ELECTRICAL
 SERIVCE IF REQUIRED".
 PLEASE SEE THAT DETERMINATIONIS TO BE
 MADE AT THIS TIME. PLEASE INDICATE SIZE
 OF EXISTING METER-CAN,SEC'S IN RISER AND
 CONDUCTORS FROM METER TO NEW MCB PANEL.
 PLEASE SEE 310.16,310.15B6,240.4 ETC.
 215.5
  
 4)NOTE: PLEASE SEE LOAD CALCULATIONS ARE
 TO DONE PER 220.31B FOR ADDITIONS TO
 EXSITING.
 PLEASE ALSO SEE A/C LOADS MUST BE
 FIGURED ON LARGEST LOADS NOT ON SMALLER
 OF THE TWO BETWEEN AHU(HEAT) AND CU.
 PLEASE SEE A/C LOADS FOR PANEL "B" AND
 SERVICE WERE TAKEN FROM LOWER COOLING
 LOADS. PLEASE SEE 220.31B, 65% MAY NOT
 BE TAKEN FOR A/C LOADS. MUST BE 100%.
  
 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR
 ADDTIONS TO EXSITING DWELLINGS. PLEASE
 SHOW ALL EXISTING OR NEW SD'S AND GFI'S
 TO MEET 2002 NEC AND NFPA-72 IN EXISTING
 DWELLING.
  
 6)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 7)NOTE: PLEASE SEE ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE ARE TO BE GFI/GFI
 PROTECTED. 210.8A6
  
 8)NOTE: PLEASE SEE ONLY ONE SMALL
 APPLIANCE CIRCUIT INDICATED ON PANEL
 SCHEDULE. PLEASE SEE 210.52B1, 210.11C1
 FOR A MIN OF TWO AND A MIN OF 1500VA PER
 CIRCUIT.
  
 9)NOTE: PLEASE SEE MISSING REQUIRED
 DEDICATED BATH CIRCUIT PER 210.11C3,
 210.52D. MUST BE 20A AND #12.
  
 10)NOTE: PLEASE SEE 20A OCP ON #14 AWG
 FOR GDO ON NEW PANEL "B".
 310.16,240.4
  
 11)NOTE:PLEASE SEE BOTH PANELS REFERENCE
 ARC FAULT PROTECTION FOR RECEPTS ONLY.
 PLEASE SEE 2002 210.12 FOR PROTECTION OF
 ALL OUTLETS IN BEDROOMS. LTS, FANS, SD'S
 RECEPTS ETC.
 PLEASE SEE NEXT NOTE ALSO.
  
 12)NOTE: PLEASE SEE SD'S ARE NOTED ON
 PLANS HOWEVER THESE ARE NOT ON PLANS.
 PLEASE SEE PREVIOUS NOTE FOR REQUIRED
 SD'S AND PLEASE SEE 210.12 FOR ARC FAULT
 PROTECTION. IF WIRED AS NOTED, THIS
 WOULD PLACE ARC FAULT PROTECTION FOR
 OTHER CIRCUITS.
  
 13)NOTE:PLEASE SEE PLANS ARE NOTED TO 99
 NEC. WE ARE UNDER THE 2002 NEC WHICH WAS
 ADOPTED ON JULY 1ST, 2003
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
  
 PLEASE BE AWARE OF ANY COMMENTS FROM
 OTHER TRADES WHICH MAY AFFECT ELECTRICAL
 PLANS. (ZONING).
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717