2005-07-11 00:00:00 | ************ UNSAT *************** |
| |
| 1)NOTE: PELASE SEE ZONING COMMENTS |
| PERTAINING TO MIN SET-BACKS REQUIRED. |
| PLEASE SEE THIS WILL AFFECT ALL PLANS |
| FOR ALL TRADES. |
| |
| 2)NOTE: PLEASE CORRELATE PANEL SCHEDULES |
| AND RISER DIAGRAM. |
| PLEASE SEE PANEL "B" SHOWS # 1 ON NEW |
| MDP AND 1/0'S ON RISER. |
| PLEASE SEE NEW PANEL "B" IS SHOWN AS |
| PANEL "E" ON RISER. |
| PLEASE ALSO SEE LABELING OF PANELS ON |
| LOAD CALCULATIONS. |
| 215.5 |
| |
| 3)NOTE: PLEASE SEE PLANS ARE NOTED TO |
| MENTION "UPGRADE EXISTING ELECTRICAL |
| SERIVCE IF REQUIRED". |
| PLEASE SEE THAT DETERMINATIONIS TO BE |
| MADE AT THIS TIME. PLEASE INDICATE SIZE |
| OF EXISTING METER-CAN,SEC'S IN RISER AND |
| CONDUCTORS FROM METER TO NEW MCB PANEL. |
| PLEASE SEE 310.16,310.15B6,240.4 ETC. |
| 215.5 |
| |
| 4)NOTE: PLEASE SEE LOAD CALCULATIONS ARE |
| TO DONE PER 220.31B FOR ADDITIONS TO |
| EXSITING. |
| PLEASE ALSO SEE A/C LOADS MUST BE |
| FIGURED ON LARGEST LOADS NOT ON SMALLER |
| OF THE TWO BETWEEN AHU(HEAT) AND CU. |
| PLEASE SEE A/C LOADS FOR PANEL "B" AND |
| SERVICE WERE TAKEN FROM LOWER COOLING |
| LOADS. PLEASE SEE 220.31B, 65% MAY NOT |
| BE TAKEN FOR A/C LOADS. MUST BE 100%. |
| |
| 5)NOTE: PLEASE SEE FBC CHAPTER 34 FOR |
| ADDTIONS TO EXSITING DWELLINGS. PLEASE |
| SHOW ALL EXISTING OR NEW SD'S AND GFI'S |
| TO MEET 2002 NEC AND NFPA-72 IN EXISTING |
| DWELLING. |
| |
| 6)NOTE: SMOKE DETECTORS ARE REQUIRED |
| INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| UNIT. |
| IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| TO FLOORS ABOVE AND IN THE VICINITY OF |
| BEDROOMS. |
| PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| A MIN OF 3' FROM BATHROOM DOORS AND |
| KITCHENS. |
| ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| |
| 7)NOTE: PLEASE SEE ALL RECEPTS SERVING |
| KITCHEN COUNTERSPACE ARE TO BE GFI/GFI |
| PROTECTED. 210.8A6 |
| |
| 8)NOTE: PLEASE SEE ONLY ONE SMALL |
| APPLIANCE CIRCUIT INDICATED ON PANEL |
| SCHEDULE. PLEASE SEE 210.52B1, 210.11C1 |
| FOR A MIN OF TWO AND A MIN OF 1500VA PER |
| CIRCUIT. |
| |
| 9)NOTE: PLEASE SEE MISSING REQUIRED |
| DEDICATED BATH CIRCUIT PER 210.11C3, |
| 210.52D. MUST BE 20A AND #12. |
| |
| 10)NOTE: PLEASE SEE 20A OCP ON #14 AWG |
| FOR GDO ON NEW PANEL "B". |
| 310.16,240.4 |
| |
| 11)NOTE:PLEASE SEE BOTH PANELS REFERENCE |
| ARC FAULT PROTECTION FOR RECEPTS ONLY. |
| PLEASE SEE 2002 210.12 FOR PROTECTION OF |
| ALL OUTLETS IN BEDROOMS. LTS, FANS, SD'S |
| RECEPTS ETC. |
| PLEASE SEE NEXT NOTE ALSO. |
| |
| 12)NOTE: PLEASE SEE SD'S ARE NOTED ON |
| PLANS HOWEVER THESE ARE NOT ON PLANS. |
| PLEASE SEE PREVIOUS NOTE FOR REQUIRED |
| SD'S AND PLEASE SEE 210.12 FOR ARC FAULT |
| PROTECTION. IF WIRED AS NOTED, THIS |
| WOULD PLACE ARC FAULT PROTECTION FOR |
| OTHER CIRCUITS. |
| |
| 13)NOTE:PLEASE SEE PLANS ARE NOTED TO 99 |
| NEC. WE ARE UNDER THE 2002 NEC WHICH WAS |
| ADOPTED ON JULY 1ST, 2003 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE BE AWARE OF ANY COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. (ZONING). |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |