Plan Review Notes For Permit 05061446 |
Permit Number |
05061446 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-29 00:00:00 | BUILDING PLAN REVIEW | | PERMIT: 05061446 | | ADD: 1500 ELIZABETH AVE | | CONT: THERMA SEAL | | TEL: (561)719-2653 | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | * WEST PALM BEACH AMENDMENTS | | | | 1ST REVIEW | | ACTION: DENIED | | REVISION CHANGE FROM A TEAR OFF TO A | | ROOF OVER OF A CONCRETE DECK. | | | | 1) FOR A ROOFOVEROF AN EXISTING | | CONCRETE DECK A PULL TEST IS REQUIRED. | | | | 2) A PREINSPECTION WILL BE REQUIRED TO | | INDICATE HOW MANY EXISTING ROOFS ARE | | THERE. | | | | 3) PAGES 6-20 ARE VARIOUS SUB SYSTEMS, | | NONE ARE HIGHLIGHTED, INDICATE WHICH | | SYSTEM WILL BE USED, DEPENDING ON THE | | SYSTEM NEG VALUES FROM 445 TO 240 ARE | | PRESENT. IF A SYSTEM IS PICKED WITH | | VALUES LESS THAN -83.7 SEE LIMITATION | | 7 OR 9. PROVIDE ENHANCED FASTENING IF | | REQUIRED. | | BUILDING PLAN REVIEW | | JIM WITMER | | TEL: (561)805-6715 | | FAX: (561)659-8026 |
|