Plan Review Notes For Permit 05061434 |
Permit Number |
05061434 |
|
Review Stop |
E |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2007-09-12 17:00:00 | ** REDLINED PLANS. | | | | NO *EQUIPMENT GROUNDING CONDUCTOR* IS PERMITTED TO BE | | INSTALLED BEFORE MAINS PER 250.6 AND 250.24B. | | THIS WAS REDLINED TO BE REMOVED IF INSTALLED AS SHOWN. |
|