Plan Review Notes
Plan Review Notes For Permit 05061434
Permit Number 05061434
Review Stop M
Sequence Number 3
Notes
Date Text
2007-08-23 20:13:02REVIEW #: 1
 ACTION: DENIED
  
 FBC 2001 CODE FAMILY W/ SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. MECHANICAL EQUIPMENT HAS CHANGED FROM ONE 6-TON
 ROOFTOP PACKAGE UNIT TO TWO 3.5-TON SPLIT SYSTEMS.
 PROVIDE REVISED ENERGY CALCULATIONS WHICH REFLECT THIS
 CHANGE.
 NOTE: BE SURE TO USE THE SAME VERSION OF THE FLA/COM
 PROGRAM WHICH WAS USED AT TIME OF PERMITTING.
  
 2. THERE ARE TWO AIR HANDLERS WITH A COMBINED DESIGN
 CAPACITY ABOVE 2000 CFM SHARING A COMMON RETURN PLENUM.
 THE RETURN AND SUPPLY AIR SYSTEMS SHALL BE PROVIDED
 WITH SMOKE DETECTORS FOR FAN SHUT-DOWN. FBC,M 606.2.2.
  
 3. PLEASE SHOW ON PLANS THE MEANS AND LOCATION OF
 CONDENSATE DISPOSAL WHICH IS IN COMPLIANCE WITH FBC,M
 307.2.
  
 4. THE LOCATION OF CONDENSING UNITS AS SHOWN ON PLANS
 WILL INTERFERE WITH THE 5 FOOT WIDE SIDEWALK AS SHOWN
 ON PG SP-1. PROVIDE REVISED SITE PLAN OR ARCHITECTURAL
 PLAN SHOWING THE LOCATION OF CONDENSERS AND VERIFY THAT
 THEY DO NOT INTERFERE WITH ANY ACCESSIBLE ROUTE WHICH
 IS REQUIRED BY FBC CH.11.
  