Plan Review Notes For Permit 05061434 |
Permit Number |
05061434 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2007-08-23 20:13:02 | REVIEW #: 1 | | ACTION: DENIED | | | | FBC 2001 CODE FAMILY W/ SUPPLEMENTS | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | 1. MECHANICAL EQUIPMENT HAS CHANGED FROM ONE 6-TON | | ROOFTOP PACKAGE UNIT TO TWO 3.5-TON SPLIT SYSTEMS. | | PROVIDE REVISED ENERGY CALCULATIONS WHICH REFLECT THIS | | CHANGE. | | NOTE: BE SURE TO USE THE SAME VERSION OF THE FLA/COM | | PROGRAM WHICH WAS USED AT TIME OF PERMITTING. | | | | 2. THERE ARE TWO AIR HANDLERS WITH A COMBINED DESIGN | | CAPACITY ABOVE 2000 CFM SHARING A COMMON RETURN PLENUM. | | THE RETURN AND SUPPLY AIR SYSTEMS SHALL BE PROVIDED | | WITH SMOKE DETECTORS FOR FAN SHUT-DOWN. FBC,M 606.2.2. | | | | 3. PLEASE SHOW ON PLANS THE MEANS AND LOCATION OF | | CONDENSATE DISPOSAL WHICH IS IN COMPLIANCE WITH FBC,M | | 307.2. | | | | 4. THE LOCATION OF CONDENSING UNITS AS SHOWN ON PLANS | | WILL INTERFERE WITH THE 5 FOOT WIDE SIDEWALK AS SHOWN | | ON PG SP-1. PROVIDE REVISED SITE PLAN OR ARCHITECTURAL | | PLAN SHOWING THE LOCATION OF CONDENSERS AND VERIFY THAT | | THEY DO NOT INTERFERE WITH ANY ACCESSIBLE ROUTE WHICH | | IS REQUIRED BY FBC CH.11. | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | RONALD J. REGUEIRO | | 561.805.6719 | | [email protected] | | | | | | |
|