2007-08-27 15:17:11*** DENIED REVISIONS***
  
 ** PLEASE SEE SOME RELINED ITEMS WHICH WERE PLACED ON
 PLANS FROM DECEMBER 05 HAVE NOT BEEN CORRECTED OR
 CHANGED.
  
 1) NOTE: PLEASE SEE THE GROUNDING ELECTRODE CONDUCTOR
 SIZE REDLINED AS THE MINIMUM OF 1/0 HAS NOT BEEN
 CORRECTED. STILL SHOWS #2.
 250.66, 250.50
  
 2) NOTE: PLEASE CLARIFY THE #2 BEING SHOWN AS THE
 EQUIPMENT GROUNDING CONDUCTORS FROM MAINS TO PANELS.
 THIS SIZE IS OK, HOWEVER MUCH LARGER THAN NEEDED.
 PLEASE BE SURE THIS IS WHAT IS INSTALLED IN THE FIELD.
  
 3) NOTE: PLEASE SEE THE SERVICES WITH TWO RISER
 REQUIRES BOTH OF THESE TO BE BONDED AS PART OF THE SAME
 GROUNDING ELECTRODE SYSTEM.
 250.50,250.66 AND 250.58
  
  