2005-12-09 00:00:00**** PLANS REDLINED ****
  
 ** PLEASE INFORM ENGINEER OF NOTE AND
 REVISE WHEN MAKING ANY OTHER CHANGES TO
 PLANS AND WHEN SUBMITTED FOR PLAN
 REVIEW.
  
  
 1)NOTE: PLEASE SEE THE PREVIOUS NOTE#4
 WAS FOR THE "EQUIPMENT GROUNDING
 CONDUCTOR", HOWEVER CHANGES TO THE
 "GROUNDING ELECTRODE CONDUCTOR" WERE
 MADE INSTEAD.
 PLEASE SEE 250.66, THE MIN SIZE FOR THE
 GEC IS 1/0.
 PLEASE SEE 250.6.250.24 FOR PERMITTED
 ATTACHMENT LOCATIONS.
  
 PLEASE SEE THE "EQUIPMENT GROUNDING
 CONDUCTORS" FROM THE FIRST MEANS OF
 DISCONNECT TO PANEL ARE OK.
  
  
 PLEASE MAKE ANY CHANGES TO THE GEC FOR
 BOTH SERVICES WITH ANY OTHER REVISIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717