Plan Review Notes
Plan Review Notes For Permit 05061434
Permit Number 05061434
Review Stop M
Sequence Number 1
Notes
Date Text
2005-07-26 00:00:00DENIED:
 1.NO MECHANICAL PLANS SUBMITTED FOR
 REVIEW.MINIMUM VENTILATION IS REQUIRED
 PER 2001 FBC(M) TABLE 403.3.PROVIDE
 CALCULATIONS ACCORDINGLY.
  
 2.PROVIDE DETAIL FOR ANY ROOF CURBS
 THAT MAY BE INSTALLED.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.