2005-07-07 00:00:00 | ************* UNSAT *************** |
| |
| 1)NOTE: PLEASE SEEBLDH #2 APPEARS TO |
| HAVE OFFICES. PLEASE PROVIDE SIGN |
| CIRCUIT PER 600.5 |
| |
| 2)NOTE: PLEASE CLARIFY OF INDEED THESE |
| WILL BE OFFICES, WILL THERE BE ANY A/C |
| UNITS? IF SO PLEASE SHOW. |
| THIS IS ONLY A NOTE: |
| |
| 3)NOTE: PLEASE SEE ROOM AT LOCATION OF |
| PANEL "J" IS LABELED AS STORAGE ON |
| A-PLANS. PLEASE ADJUST RM DESIGNATION AS |
| ELECTRICAL RM/ NO STORAGE ON PLANS AT |
| BOTH LOCATION. 110.26,408.7 |
| |
| 4)NOTE: PLEASE SEE 250.6,250.24. |
| EQUIPMENT GROUNDING CONDUCTORS SHALL NOT |
| BE INSTALLED UNTIL AFTER THE FIRST MEANS |
| OF DISCONNECT. PLEASE SEE RISER SHOWS A |
| 1/0 AS AN EQUIPMENT GROUNDING CONDUCTOR |
| FROM GUTTER TO METER AND METER TO FIRST |
| MEANS OF DISC. |
| |
| 5)NOTE: PLEASE SEE PLUMB REVIEW NOTES |
| FOR ENGINEER'S SIGNATURE OF RECORD ON |
| PLUMB SHEETS. |
| |
| PLEASE SEE ANY OTHER POSSIBLE COMMENTS |
| FROM OTHER REVIEWER(S) WHICH MAY AFFECT |
| ELECTRICAL PLANS. |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEWL. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE IN CONTACTING |
| THIS OFFICE. |
| |