2005-07-16 00:00:00 | DENIED |
| REFERENCE: FBC-2001 PLUMBING |
| FBC-2001 CHAPTER 1 |
| FBC-2001 CHAPTER 11 |
| |
| 1. SHT A-1.0 AN RPZ BACKFLOW IS REQUIRED |
| ON THE WATER SERVICE FOR THE TRAILERS. |
| SHOW WATER SERVICE AND BACKFLOW ON |
| PLANS. |
| 2. SHT A-1.0 INDICATES A SANITARY |
| HOLDING TANK. A PERMIT FROM THE COUNTY |
| HEALTH DEPT. IS REQUIRED FOR THE HOLDING |
| TANK. PLEASE CONTACT FRANK LOMBARDO |
| (561) 233-5139. PERMIT SHALL BE |
| SUBMITTED WITH PLANS WHEN RESUBMITTING |
| FOR REVIEW FOR PERMIT. SECTION 104.7.1 |
| 3. SHT A-2.0 SHOW THE CLEAR FLOOR SPACE |
| FOR THE FOLLOWING: |
| A. 11-4.15.5 WATER COOLER |
| B. 11-4.16.2 WATER CLOSETS |
| C. 11-4.19.3 LAVS |
| 4. SHT A-3.0 RESTROOM DETAILS - SHOW THE |
| FOLLOWING: |
| (FOR W/C'S) |
| A. 11-4.16.5 FLUSH CONTROLS |
| B. 11-4.16.6 DISPENSERS |
| (FOR LAVS) |
| A. 11-4.19.4 EXPOSED PIPES & SURFACES |
| B. 11-4.19.5 FAUCETS |
| 5. WATER COOLER SHALL BE ARI-1010 |
| COMPLIANT. SUBMIT MANUF. SPECIFICATION |
| SHEETS. |
| 6. SHT M-2 WATER RISER DIAGRAM. AIR |
| CHAMBERS ARE NOT APPROVED. DELETE FROM |
| RISER. SECTION 604.9. - THERMAL |
| EXPANSION CONTROL IS REQUIRED. SECTION |
| 607.3.2. SHOW HOW THIS IS BEING |
| ADDRESSED. |
| 7. SEPARATE IRRIGATION PLANS & PERMIT IS |
| REQUIRED. SECTION 104.3.1.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 653-2692 |
| E-MAIL [email protected] |