Notes |
Date |
Text |
2005-07-20 00:00:00 | ******DENIED****** | | | | 1) ALL CONSTRUCTION, ALTERATION AND | | DEMOLITION TO COMPLY WITH NFPA 241. | | | | 2) AN ADDRESS IS REQUIRED ON THE | | BUILDING, AND MUST BE AT LEAST 6" IN | | HEIGHT AND CONTRASTING WITH THE | | BACKGROUND. | | | | 3) PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | REQUIREMENT FOR GUARDS AND HANDRAILS. | | | | 4) PLEASE PROVIDE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | 5) PLEASE INDICATE LOCATION AND DISTANCE | | FROM PROJECT TO NEAREST FIRE HYDRANT. | | | | | | MIKE WENNERGREN, CAPTAIN | | WPBFR(561) 805-6722 OR 804-4756 |
|