Plan Review Notes For Permit 05061350 |
Permit Number |
05061350 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-11 00:00:00 | DENIED; | | 1.WATER SUPPLY LOCAL ORD. # 2853-95 | | BACKFLOW REQUIRED ON WATER SERVICE. | | 2.ADD NO AIR TEST TONOTE NUMBER 4. | | 3.JOINTS AND CONNECTIONS FBC 605.21 | | PURPLE PRIMER REQUIRED ON PVC PIPES AND | | FITTINGS.4. | | 4.CONECTIONS ALL WATER HEATING EQUIPMENT | | SHALL BE INSTALLED WITH FLANGES OR UNION | | CONNECTIONS ADJACENT TO HEATER. | | 5.GAS PIPING SHALL COMPLY WITH FBC FUIL | | GAS. SEPARATE PLANS AND PERMIT REQUIRED. | | ( ADD TO NOTES ALL) |
|