Plan Review Notes For Permit 05061193 |
Permit Number |
05061193 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-30 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} SUBMIT GENERATOR AND TRANSFER SWITCH | | MANUFACTURERS SPECIFICATIONS. 2 COPIES. | | | | 2} THE #3 FEEDERS MAY NOT BE LARGE | | ENOUGH TO COMPLY WITH 445.13 NEC.(115%). | | DON'T KNOW NAMEPLATE RATING WITHOUT | | SPEC'S AND PRIME MOVER. | | | | 3} CALCULATED LOAD PER 702.5. WILL | | ACCEPT OPTIONAL CALCULATION 220.31(B) | | FOR EMERGENCY PANEL. | | | | 4} PLEASE SHOW THE LOCATION OF THE | | TRANSFER SWITCH ON THE FLOOR PLAN | | DRAWING SO COMPLIANCE WITH 225.32 CAN BE | | DETERMINED. | | | | 5} DESIGNER MUST PRINT NAME AND SIGN | | PLANS, 104.2.1 FBC. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 |
|