Date Text
2005-06-30 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} SUBMIT GENERATOR AND TRANSFER SWITCH
 MANUFACTURERS SPECIFICATIONS. 2 COPIES.
  
 2} THE #3 FEEDERS MAY NOT BE LARGE
 ENOUGH TO COMPLY WITH 445.13 NEC.(115%).
 DON'T KNOW NAMEPLATE RATING WITHOUT
 SPEC'S AND PRIME MOVER.
  
 3} CALCULATED LOAD PER 702.5. WILL
 ACCEPT OPTIONAL CALCULATION 220.31(B)
 FOR EMERGENCY PANEL.
  
 4} PLEASE SHOW THE LOCATION OF THE
 TRANSFER SWITCH ON THE FLOOR PLAN
 DRAWING SO COMPLIANCE WITH 225.32 CAN BE
 DETERMINED.
  
 5} DESIGNER MUST PRINT NAME AND SIGN
 PLANS, 104.2.1 FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  