Plan Review Notes
Plan Review Notes For Permit 05061058
Permit Number 05061058
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-05 00:00:00BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6716
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2001
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1507.4.3ROOF TILE UNDERLAYMENT.
 PROPOSED ADHESIVE SET CONCTRETE TILE.
 THE SUBMITTED EAVE DETAIL SHOWS
 "SELF-ADHERED UNDERLAYMENT OVER EXISTING
 PLYWOOD DECK".NO PRODUCT APPROVAL WAS
 SUBMITTED FOR THE SPECIFIED POLYGLASS
 POLYSTICK TU.REFERENCE TO THE FLORIDA
 STATE PRODUCT APPROVAL LISTING AND THE
 INSTALLATION INSTRUCTIONS ON THE
 ASSOCIATED MIAMI-DADE PRODUCT APPROVAL
 NOA# 02-0603.08 SHOWS THAT POLYSTICK TU
 IS TO BE APPLIED OVER A BASE SHEET OF
 "ONE OR MORE PLIES OF ASTM D 226 TYPE II
 OR ASTM D 2626" NAILED AND TIN-CAPPED AT
 12" O.C., 6" O.C. AT LAPS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO
 TELEPHONE: (561) 805 6716ROBERT BROWN
 E-MAIL: [email protected]