Plan Review Notes For Permit 05061017
Permit Number 05061017
Review Stop E
Sequence Number 4
Notes
Date Text
2006-06-22 00:00:00** PLANS REDLINED **
  
 TO VERIFY OF PC/ MPDEM RM IS INDEED AN
 "IT" ROOM WHICH WILL REQUIRE RATING S
 FOR CONSTRUCTION, DISCONNECTS ETC.
 PLEASE SEE 645 OF NFPA-70, AND NFPA-75
 FOR REQUIREMENTS ALSO IN "IT" ROOMS.
 ENGINEER OR RECORD HAS SEALED PLANS NOT
 AS AN IT ROOM.
  
  
 ** PLEASE KNOW, AS NOTED ON PREVIOUS
 REVIEW, THIS ROOM WAS NOT ON ORIGINAL
 PLANS AND WAS ADDED DURING CONSTRUCTION.
 IF AN "IT", REVISED PLANS WILL BE
 REQUIRED TO BE SUBMITTED FOR B,M,F, E.
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]