Plan Review Notes
Plan Review Notes For Permit 05061017
Permit Number 05061017
Review Stop E
Sequence Number 3
Notes
Date Text
2006-04-25 00:00:00************UNSAT ***************
  
 1) NOTE: PLEASE SEE PLANS WHICH WERE
 REDLINED TWICE BEFORE THIS REVIEW WHICH
 REQUESTED KITCHENS IN OTHER THAN
 DWELLING UNITS TO MEET 210.8B3
 PLEASE ADJUST.
  
 2) NOTE: PLEASE PROVIDE ALL ROOM AND
 AREA DESIGNATIONS ON PLANS.
 PLEASE SEE AN "IT" ROOM WAS NOT
 IDENTIFIED ON ORIG ELECTRICAL PLANS.
 PLEASE SEE ALL OF NEC 645, NFPA-75 FOR
 MIN REQUIRMENTS.
 PLEASE SEE 645.10,645.5,645.2.
 PLEASE ADJUST ACCORDINGLY.
  
 3) NOTE: PLEASE SEE RISER WHICH INDICATE
 ONE RISER OF 3-3/0'S OR 500MCM'S, WHICH
 IS ALSO NOTED AS BEING DONE BY FPL, OR
 MAYBE BY FPL.
 PLEASE KNOW, THE WH, RISER, ETC UP TO
 THE SERVICE ENTRANCE DRIP LOOP BELONGS
 TO THE OWNER OF THE BUILDING, NOT FPL.
 FPL WILL NOT BE INSTALLING THIS RISER.
 PLEASE SPECIFY WHICH OPTION FOR RISER
 WAS OR IS BEING INSTALLED.
 THIS WAS REDLINED ON PREVIOUS PLANS.
 215.5.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved