Plan Review Notes For Permit 05061017 |
Permit Number |
05061017 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-10-01 00:00:00 | DENIED; | | 1. SHEET D-1 ADD TO NOTES DEAD ENDS TO | | BE 2' OR LESS, FIELD INSPECTION | | REQUIRED. | | 2.WOMEN'S ROOM; SHOW THE CLEAR FLOOR | | SPACE FOR THE TOILET ROOM IN THE TOILET | | ROOM NOT IN THE STALL. | | 3.BREAK SINK DOES NOT COMPLY WITH FBC | | CHAPTER 11 SEC. 11-4.24.3 KNEE CLEARANCE | | SHALL BE 19" UNDERNEATH SINK. LOWER | | FRONT PANEL CAN NOT BE INSTALLED AS | | DRAWN. | | PLUMBING PLAN REVIEW BY; | | JOHN LEECH | | 805-6695 |
|