Plan Review Notes
Plan Review Notes For Permit 05061017
Permit Number 05061017
Review Stop M
Sequence Number 2
Notes
Date Text
2005-11-21 00:00:00PROVISO:
 1. PLAN SHEET M-1 PER 2001 FBC(M)501.3,
 EXHAUST SHALL TERMINATE AT A LOCATION AS
 NOT TO BE READILY DRAWN IN BY THE
 VENTILATING SYSTEM.EXHAUST TERMINATION
 APPEAR TO TERMINATE UNDERNEATH THE FRESH
 AIR INTAKE TO AHU-1.PLEASE REVISE
 PLANS PRIOR TO INSPECTION.
  
 2. FAN SHUTDOWN REQUIRED FOR AHU-1 PER
 2001 FBC(M)606.2.1.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561)805-6719.