Plan Review Notes For Permit 05061017 |
Permit Number |
05061017 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-09-03 00:00:00 | ********* NOTES REDLINED ********* | | | | 1)NOTE: PLEASE SEE PREVIOUS REVIEW, | | PLANS WERE REDLINED FOR 2002 NEC 210.8B3 | | WHICH REQUIRES ALL 15A& 20A RECEPTS IN | | KITCHEN/LUNCH RM AREA TO BE GFI OR GFI | | PROTECTED CIRCUITS. | | | | THIS WAS RED LINED PLANS ONCE AGAIN. | | PLEASE KNOW, IF PLANS COME BACK DURING | | CONTRUCTION FOR ANY OTHER REVISIONS, | | PLEASE MAKE CORRECTIONS. | | | | NEW SHEETS E-1 AND E-2 SUBMITTED. |
|