Plan Review Notes For Permit 05061017
Permit Number 05061017
Review Stop P
Sequence Number 1
Notes
Date Text
2005-07-12 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
  
 1. SHT D-1 IN THE REMOVAL OF ANY PART OF
 A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. SECTION 704.5 - ALL CAPPED
 OFF PIPING SHALL BE FIELD INSPECTED
 PRIOR TO COVERING.
 2. SHT A-1 SHOW CLEAR FLOOR SPACE FOR
 THE SINK IN THE LUNCHROOM. SECTION
 11-4.24.5. SINK SHALL BE CENTERED ON THE
 30" WIDTH.
 3. SHT A-1 SHOW THE CLEAR FLOOR SPACE
 FOR THE TOILET ROOMS IN THE TOILET ROOM,
 NOT THE STALL. SECTION 11-4.22.3
 4. SHT A-5 BREAKROOM SINK SHALL BE
 ACCESSIBLE. PROVIDE THE FOLLOWING
 INFORMATION ON DETAIL 3/A5 TO SHOW
 COMPLIANCE:
 A. 11-4.24.2 HEIGHT
 B. 11-4.24.3 KNEE CLEARANCE
 C. 11-4.24.4 SINK DEPTH
 D. 11-4.24.5 CLEAR FLOOR SPACE SHALL BE
 PROVIDED TO ALLOW FORWARD APPROACH AND
 SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH
 THE SINK. - CABINET DOORS SHALL NOT BE
 IN THE CLEAR FLOOR SPACE.
 E. 11-4.24.6 EXPOSED PIPES & SURFACES
 F. 11-4.24.7 FAUCETS
 5. SHT P2 WATER RISER DIAGRAM, AIR
 CHAMBERS ARE NOT APPROVED, DELETE FROM
 RISER DIAGRAM. SECTION 604.9. - WATER
 HAMMER ARRESTORS SHALL BE LOCATED NEAR
 THE FIXTURES IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 201 AND
 MANUF. INSTALLATION INSTRUCTIONS.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]
  
  
  
  
  
  
  