Plan Review Notes For Permit 05061017 |
Permit Number |
05061017 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-11 00:00:00 | 1. DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 2. DEBRIS SHALL BE REMOVED FROM THE | | SITE DAILY. | | | | 3. ON PAGE M1 THERE APPEARS TO BE A/C | | DUCTWORK WITHIN THE EXIT STAIR. IF SO, | | NOT ALLOWED BY CODE. PLEASE EXPLAIN. | | | | 4. PLEASE PROVIDE PRESCRIPTIVE STRENGTH | | REQUIREMENTS FOR HANDRAILS. | | | | 5. TEN (10) INCH TREADS SHOWN ON PAGE | | A-4. TEN INCH TREADS ARE NOT ALLOWED | | FOR NEW STAIRS. | | | | 6. FIRE ALARM SYSTEM SHALL BE CLASS A OR | | FULLY ADDRESSABLE. | | | | 7. ELEVATION DRAWINGS DO NOT DISPLAY | | BUILDING ADDRESS. BUILDING ADDRESS SHALL | | BE A MINIMUM OF AT LEAST 6" HIGH | | NUMBERS. | | | | 8. WHAT FIRE RATING IS PRESENT FOR THE | | STAIRWELL DOOR LOCATED ON THE SECOND | | LEVEL NEAR FAX PRINTER AREA. | | | | 9. PLEASE ILLUSTRATE FIRE EXTINGUISHER | | LOCATIONS. | | | | 10. PLEASE INDICATE INTERIOR FINISH | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER. | | 835-2910 |
|