2005-07-24 00:00:00 | BUILDING PLAN REVIEW |
| PERMIT: 05061017 |
| ADD: 2813 EXCHANGE CT |
| CONT: SOUTHHAMPTON RESTORATION |
| TEL: (561)687-0505 |
| |
| 2001 FL BLDGFLORIDA BUILDING CODE |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1ST REVIEW |
| ACTION: DENIED |
| |
| 1)PRODUCT APPROVALS SUBMITTED WITH |
| PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| PLEASE SEE THE STATE WEBSITE AT |
| WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| STATEWIDE APPROVAL ARE REQUIRED TO BE |
| SUBMITTED WITH A COVER SHEET THAT LISTS |
| THE PRODUCT IDENTITY NUMBER FROM THE |
| STATE. IF THE PRODUCT DOES NOT HAVE |
| STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| SPECIFIC FORM PER RULE 9B-72. SEE |
| ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| |
| 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| TESTING REPORTS,MISSING REPORTS ARE AS |
| FOLLOWS: |
| A) WINDOWS |
| B) MULLION |
| |
| 3) PLANS DO NOT PROVIDE CLASSIFICATION |
| BY TYPE OF BUILDING 601.2.1. PLANS ALSO |
| DO NOT PROVIDE IF FIRE SPRINKLERED? A-3 |
| INDICATES A FIRE SPRINKLER RISER ON THE |
| EXTERIOR OF BUILDING, IS ACTIVE? |
| |
| 4) PROVIDE INFORMATION ON CHAIRLIFT? |
| TO COMPLY WITH ASME A 17.1. |
| |
| 5) IF BUILDING IS NOT FIRE SPRINKLERED, |
| THEN ARTICLES DEALING WITH AREA OF |
| RESCUE ASSISTANCE ARE REQUIRED. |
| SEE 11-4.3.11.1.(1-7). |
| |
| 6)SEE A.1 LUNCHROOM INDICATES SECTION 3 |
| BUT NO SECTION APPEARS FOR LUNCH COUNTER |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE |
| MOUNTED WITH THE COUNTER NO HIGHER THAN |
| 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARENCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| |
| |
| 7)M1 INDICATES A A/C GRILL IN THE |
| STAIRWELL, SEE 1006.1.3.1. |
| |
| 8) DOOR# 9 REQUIES 18" CLEAR ON THE |
| LATCH SIDE. 11-4.13.6 MANEUVERING |
| CLEARENCES AT DOORS. MINIMUM MANEUVERING |
| CLEARENCES AT DOORS THAT ARE NOT |
| AUTOMATIC OR POWER-ASSISTED SHALL BE AS |
| SHOWN IN FIG. 25. THE FLOOR OR GROUND |
| AREA WITH IN THE REQUIRED CLEARENCES |
| SHALL BE CLEAR & LEVEL. |
| BUILDING PLAN REVIEW |
| JIM WITMER |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| |