Plan Review Notes
Plan Review Notes For Permit 05061017
Permit Number 05061017
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 05061017
 ADD: 2813 EXCHANGE CT
 CONT: SOUTHHAMPTON RESTORATION
 TEL: (561)687-0505
  
 2001 FL BLDGFLORIDA BUILDING CODE
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) MULLION
  
 3) PLANS DO NOT PROVIDE CLASSIFICATION
 BY TYPE OF BUILDING 601.2.1. PLANS ALSO
 DO NOT PROVIDE IF FIRE SPRINKLERED? A-3
 INDICATES A FIRE SPRINKLER RISER ON THE
 EXTERIOR OF BUILDING, IS ACTIVE?
  
 4) PROVIDE INFORMATION ON CHAIRLIFT?
 TO COMPLY WITH ASME A 17.1.
  
 5) IF BUILDING IS NOT FIRE SPRINKLERED,
 THEN ARTICLES DEALING WITH AREA OF
 RESCUE ASSISTANCE ARE REQUIRED.
 SEE 11-4.3.11.1.(1-7).
  
 6)SEE A.1 LUNCHROOM INDICATES SECTION 3
 BUT NO SECTION APPEARS FOR LUNCH COUNTER
 11-4.24.2 SINKS, HEIGHT. SINKS SHALL BE
 MOUNTED WITH THE COUNTER NO HIGHER THAN
 34" ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARENCE THAT IS AT
 LEAST 27" HIGH 30" WIDE, AND 19" DEEP
 SHALL BE PROVIDED UNDERNEATH SINKS.
  
  
 7)M1 INDICATES A A/C GRILL IN THE
 STAIRWELL, SEE 1006.1.3.1.
  
 8) DOOR# 9 REQUIES 18" CLEAR ON THE
 LATCH SIDE. 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING
 CLEARENCES AT DOORS THAT ARE NOT
 AUTOMATIC OR POWER-ASSISTED SHALL BE AS
 SHOWN IN FIG. 25. THE FLOOR OR GROUND
 AREA WITH IN THE REQUIRED CLEARENCES
 SHALL BE CLEAR & LEVEL.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026
  