2005-08-23 00:00:00DENIED
  
 1) PLEASE REVISE THE ANCHOR SCHEDULE ON
 A5. THE MAXIMUM UPLIFT FOR A USP HTA 16
 CONNECTOR IS 1500#. THE DOUBLE HTA 16
 HAS A MAXIMUM UPLIFT OF 3000#. THESE ARE
 THE VALUES LISTED IN THE 2005 USP
 CATALOG AND DO NOT INCLUDE THE ONE THIRD
 STRESS INCREASE ON THE STEEL
 CALCULATIONS WHICH IS NOT ALLOWED BY THE
 2001 FBC. SEE FBC 1609.4.3. SEE ITEM #6
 ON PREVIOUS REVIEW.
  
 2) THE DESIGN PRESSURES REQUIRED BY THE
 PLANS FOR THE SMALL GARAGE DOOR EXCEED
 THE DESIGN PRESSURES GIVEN IN THE
 PRODUCT APPROVAL THAT WAS SUBMITTED.
 SUBMIT PRODUCT WITH ADEQUATE DESIGN
 PRESSURES. SEE COMMENT # 8 FROM PREVIOUS
 REVIEW.
  
 3) THE PRODUCT APPROVALS SUBMITTED FOR
 THE FIXED GLASS WINDOWS ARE FOR
 NON-IMPACT RESISTANT GLAZING. THE PLANS
 SPECIFY IMPACT GLAZING FOR ALL WINDOWS.
 SUBMIT PRODUCT APPROVALS FOR IMPACT
 WINDOWS OR REVISE PLANS AND SUBMIT STORM
 PANEL PRODUCT APPROVALS, KEY PLANS AND
 INSTALLATION SCHEDULES.
  
 4)IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
  