2005-08-23 00:00:00 | DENIED |
| |
| 1) PLEASE REVISE THE ANCHOR SCHEDULE ON |
| A5. THE MAXIMUM UPLIFT FOR A USP HTA 16 |
| CONNECTOR IS 1500#. THE DOUBLE HTA 16 |
| HAS A MAXIMUM UPLIFT OF 3000#. THESE ARE |
| THE VALUES LISTED IN THE 2005 USP |
| CATALOG AND DO NOT INCLUDE THE ONE THIRD |
| STRESS INCREASE ON THE STEEL |
| CALCULATIONS WHICH IS NOT ALLOWED BY THE |
| 2001 FBC. SEE FBC 1609.4.3. SEE ITEM #6 |
| ON PREVIOUS REVIEW. |
| |
| 2) THE DESIGN PRESSURES REQUIRED BY THE |
| PLANS FOR THE SMALL GARAGE DOOR EXCEED |
| THE DESIGN PRESSURES GIVEN IN THE |
| PRODUCT APPROVAL THAT WAS SUBMITTED. |
| SUBMIT PRODUCT WITH ADEQUATE DESIGN |
| PRESSURES. SEE COMMENT # 8 FROM PREVIOUS |
| REVIEW. |
| |
| 3) THE PRODUCT APPROVALS SUBMITTED FOR |
| THE FIXED GLASS WINDOWS ARE FOR |
| NON-IMPACT RESISTANT GLAZING. THE PLANS |
| SPECIFY IMPACT GLAZING FOR ALL WINDOWS. |
| SUBMIT PRODUCT APPROVALS FOR IMPACT |
| WINDOWS OR REVISE PLANS AND SUBMIT STORM |
| PANEL PRODUCT APPROVALS, KEY PLANS AND |
| INSTALLATION SCHEDULES. |
| |
| 4)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |