2005-06-22 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE RISER SHOWS PANELS WITH MAIN
 BREAKERS, PLAN SHOWS MAIN DISCONNECTS
 OUTSIDE AND PANELS INSIDE. PLEASE
 CLARIFY.
  
 2} PANEL "C" IS FED FROM PANEL "B" ON
 THE RISER, BUT OUT OF PANEL "A"ON THE
 SCHEDULE.
  
 3} INDICATE THE AIC RATING OF THE
 SERVICE EQUIPMENT PER 110.9 & 10.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  