Date |
Text |
2005-07-15 00:00:00 | DENIED |
| |
| 1)IMPACT FEES MUST BE PAID TO PALM |
| BEACH COUNTY, PLANS STAMPED BY THEM AND |
| COPY OF RECEIPT SUBMITTED TO CITY OF |
| WEST PALM BEACH BUILDING DEPARTMENT, |
| BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| |
| 2) ITEM #4 IN THE DOOR SCHEDULE ON A2 IS |
| LISTED AS A SLIDING GLASS DOOR AND ON |
| THE PLAN IT IS DRAWN AS A DOUBLE |
| OUTSWING FRENCH DOOR AT THE FAMILY ROOM. |
| |
| 3) ITEM #16 IN THE SCHEDULE IS ANOTHER |
| SLIDING GLASS DOOR AND THERE AREN'T ANY |
| SG DOORS ON THE PLANS. PLEASE CORRECT. |
| ALSO REMOVE THE PRODUCT APPROVALS FOR |
| SLIDING GLASS DOORS FROM THE SUBMITTALS |
| AS IT DOES NOT APPLY TO THIS PROJECT. |
| |
| 4) PLEASE UPDATE DESIGN CRITERIA ON A5. |
| THE REFERENCED STANDARDS IN THE 2OO1 FBC |
| ARE ACI 318-02 AND ACI530.1-02. SEE FBC |
| CHAPTER 35. |
| |
| 5) ON A5 THERE IS A CONNECTOR AT THE |
| COVERED PATIO WITH A #12 TAG. THERE IS |
| NO #12 SPECIFIED IN THE ANCHOR LEGEND. |
| PLEASE CLARIFY. |
| |
| 6) PLEASE REVISE THE ANCHOR SCHEDULE ON |
| A5, AS SEVERAL CONNECTOR UPLIFTS |
| SPECIFIED ARE IN ERROR. THE MAXIMUM |
| UPLIFT FOR HTA 16 IS 1500#. THE DOUBLE |
| HTA 16S HAVE A MAXIMUM UPLIFT OF 3000#. |
| THE MAX. UPLIFTS FOR THE 'USP' RT22T AND |
| RT20T ARE 1225#. SEE 2005 USP CATALOG. |
| |
| 7) PROVIDE STRUCTURAL DETAILS OF THE |
| CUPOLA ABOVE THE MASTER BEDROOM. SPECIFY |
| ALL CONNECTORS, EXTERIOR AND INTERIOR |
| FINISHES, STUD SIZE AND SPACING, |
| INSULATION, ETC. |
| |
| 8) THE DESIGN PRESSURES REQUIRED BY THE |
| PLANS FOR THE SMALL GARAGE DOOR EXCEED |
| THE DESIGN PRESSURES GIVEN IN THE |
| PRODUCT APPROVAL THAT WAS SUBMITTED. |
| |
| 9) SUBMIT PRODUCT APPROVALS FOR THE |
| HOLLOW METAL DOOR AT THE MECHANICAL |
| ROOM, # 17 IN THE SCHEDULE. |
| |
| 10) SUBMIT PRODUCT APPROVALS FOR THE |
| STORE FRONT WINDOWS (H,I,AND D IN THE |
| SCHEDULE). |
| |
| 11) ITEM #5 IN THE DOOR SCHEDULE IS |
| SPECIFIED AS A STORE DOOR. PLEASE |
| CLARIFY AND SUBMIT THE APPROPRIATE |
| PRODUCT APPROVAL. |
| |
| ROBERT MCDOUGAL |
| BLDG. PLAN REVIEW |
| (561)805-6714 |
| |
| |
| |