Date |
Text |
2005-06-13 00:00:00 | DENIED |
| BUILDING PLAN REVIEW |
| *******DENIED******* |
| MYRON JACOBS(561) 805 6726 |
| E-MAIL: [email protected] |
| |
| FBC = FLORIDA BUILDING CODE 2001 |
| FBC*= FLORIDA BUILD'G CODE (CITY AMEND) |
| F.S.= FLORIDA (STATE) STATUTE |
| |
| 1) FBC 1606.2.5THE SYSTEM SELECTED |
| FROM THE SUBMITTED FLAT ROOF PRODUCT |
| APPROVAL NOA HAS A MAXIMUM DESIGN |
| PRESSURE OF LESS THAN -89 PSF AND CITES |
| GENERAL LIMITATION #9 (SEE PAGE9OF28). |
| GENERAL LIMITATION #9 PROHIBITS RATIONAL |
| ANALYSIS OR EXTRAPOLATION TO ENHANCE THE |
| UPLIFT PRESSURE AT PERIMETER AND CORNER |
| AREAS BY REDUCING THE FASTENER SPACING |
| IN THESE AREAS.EITHER SELECT AN |
| ALTERNATIVE SYSTEM (OR PRODUCT APPROVAL) |
| THAT DOES NOT CITE GENERAL LIMITATION |
| #9.ALTERNATIVELY IF THE SELECTED |
| SYSTEM DOES CITE GENERAL LIMITATION #9, |
| IT MUST HAVE A MAXIMUM DESIGN PRESSURE |
| THAT EXCEEDS THE PRESSURE IN ROOF ZONE 3 |
| (TYPICALLY -89 PSF FOR MEAN ROOF HEIGHT |
| OF 30 FEET OR LESS).YOU MAY REVIEW THE |
| SUBMITTED REPORT FOR A SYSTEM WHICH DOES |
| NOT REFER TO GENERAL LIMITATION #9. |
| |
| BUILDING PLAN REVIEW |
| MYRON JACOBS |
| TEL: (561)805-6726 |
| FAX: (561)659-8026 |
| [email protected]. |