Plan Review Notes For Permit 05060882 |
Permit Number |
05060882 |
|
Review Stop |
E |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-08-10 00:00:00 | ********** NOTES REDLINED************** | | | | PLEASE KNOW, GENERATOR AS SHOWN ON RISER | | DIAGRAM ALONG WITH ALL CONDUITS AND | | CONDUCTORS UP TO ATS SWITCH IS NOT | | INCLUDED ON THIS PERMIT. | | WHEN GENERATOR IS PERMITTED IN THE | | FUTURE, ALL DISCONNECTING MEANS FOR | | GENERATOR FEEDERS INTO THE BUILDING | | SHALL BE GROUPED WITH EXISTNG MAINS. | | 225.31-225.36 | | | | IF THERE ARE ANY QUESTIONS, PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|