Plan Review Notes
Plan Review Notes For Permit 05060882
Permit Number 05060882
Review Stop E
Sequence Number 2
Notes
Date Text
2005-08-02 00:00:00********** UNSAT *********
  
 PLEASE SEE SOME NOTES FROM FIRST REVIEW.
  
 1)NOTE: PLEASE SEE PREVIOUS NOTE #1
 WHICH REQUIRED THE ENGINEER TO SIGN
 PLANS. THIS WAS DONE ONLY ON NEW REVISED
 ELECTRICAL SHEETS AND NOT FOR OLD SHEETS
 IN SETS. PLEASE ALSO SEE FP SHEETS.
 THIS IS REQUIRED OF ALL SHEETS AND FOR
 ALL TRADES WHEATHER OR NOT COMMENT IS
 MADE BY OTHER TRADES.
 FS 471.025
  
 2)NOTE: PLEASE SEE ONLY ONE COPY OF
 SPECS FO ATS WERE SUBMITTED.
  
 3)NOTE: PLEASE KNOW, GENERATOR IS NOTED
 ON PLANS "BY OTHERS", PLEASE KNOW, NO
 CONDUITS, CONDUCTOS, MAINS ETC SHALL BE
 PERMITTED AT THIS TIME. ONLY THE ATS MAY
 BE INSTALLED AND NORMAL LINE AND LOAD.
 215.5
  
  
 PLEASE REMOVE OLD/VOIDED SHEETS FROM
 SETS AND ONLY INSERT NEW REVISED SHEETS
 INTO COMPLETE SETS FOR REVIEW AND
 STAMPING. ONE COPY OF ANY OLD/VOIDED
 SHEETS SHOULD BE SUBMITTED FOR REFERENCE
 ONLY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]