2005-07-11 00:00:001. SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE SPRINKLER SYSTEM REMODEL.
  
 2. FIRE ALARM NOTES ON PAGE FA0.1 ARE
 INCORRECT. NOTES # 17 AND 19 ARE NOT
 CORRECT. PLEASE REVISE NOTES.
  
 3. SEPARATE PLANS AND PERMITS REQUIRED
 FOR FIRE ALARM EQUIPMENT REMODEL.
  
 4. NO COMBUSTIBLES ALLOWED IN ANY
 RETURN AIR PLENUMS.
  
 5. DEMOLITION, RENOVATION, AND
 CONSTRUCTION TO COMPLY WITH NFPA 241.
  
 6. COULD NOT LOCATE ANY INFORMATION
 REGARDING FIRE RATING FOR DOORS INTO
 COMMON AREAS OF THE BUILDING. PLEASE
 PROVIDE DETAILS.
  