Plan Review Notes For Permit 05060882 |
Permit Number |
05060882 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-11 00:00:00 | 1. SEPARATE PLANS AND PERMIT REQUIRED | | FOR FIRE SPRINKLER SYSTEM REMODEL. | | | | 2. FIRE ALARM NOTES ON PAGE FA0.1 ARE | | INCORRECT. NOTES # 17 AND 19 ARE NOT | | CORRECT. PLEASE REVISE NOTES. | | | | 3. SEPARATE PLANS AND PERMITS REQUIRED | | FOR FIRE ALARM EQUIPMENT REMODEL. | | | | 4. NO COMBUSTIBLES ALLOWED IN ANY | | RETURN AIR PLENUMS. | | | | 5. DEMOLITION, RENOVATION, AND | | CONSTRUCTION TO COMPLY WITH NFPA 241. | | | | 6. COULD NOT LOCATE ANY INFORMATION | | REGARDING FIRE RATING FOR DOORS INTO | | COMMON AREAS OF THE BUILDING. PLEASE | | PROVIDE DETAILS. | | | | MIKE CARSILLO, CHIEF FIRE PREVENTION | | OFFICER | | 835-2910 |
|