Plan Review Notes
Plan Review Notes For Permit 05060882
Permit Number 05060882
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-27 00:00:00************** UNSAT ****************
  
 1)NOTE: PLEASE SEE ELECTRICAL SHEETS ARE
 TO BE SIGNED BY THE ENGINEER OF RECORD.
 INITIALS ARE NOT ACCEPTIBLE.
 FS 471.025
  
 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE
 CUT/SPEC SHEETS FOR ATS (S) TO BE
 INSTALLED.
 PLEASE SEE 225.36, THIS SHALL BE SERVICE
 ENT RATED. PLEASE SEE GEN IS NOT PART OF
 THIS PERMIT APPLICATION. PLEASE SEE
 GROUPING OF DISCONNECTING MEANS WILL BE
 REQUIRED WITH EXISTING MAINS ETC.
 225.34
 GEN IS TO BE SUBMITTED UNDER SEPARATE
 PERMIT IF NOT IN THIS SCOPE OF WORK.
 GEN WILL NOT BE PERMITTED AT LOCATION
 /FLR AS SHOWN ON PLANS FOR FUTURE
 PERMIT.
  
 3)NOTE: PLEASE SEE ELECTRICAL ROOM DOES
 NOT SEEM TO SHGOW MIN CLEARENCE REQUIRED
 UNDER 110.26.
  
 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS
 AT 125%. 215.3,230.42, ETC.
  
 5)NOTE: PLEASE SHOW GROUNDING FOR
 TRANSFORMER 250.30
  
 PLEASE REMOVE ALL OLD/VOIDED SHEETS AND
 ONLY INSERT NEW REVISED SHEETS INTO
 COMPLETE SETS FOR REVIEW AND STAMPING.
 ONE SET OF OLD/VOIDED SHEETS SHOULD BE
 SUBMITTED FOR REFERENCE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]
  