2005-06-27 00:00:00 | ************** UNSAT **************** |
| |
| 1)NOTE: PLEASE SEE ELECTRICAL SHEETS ARE |
| TO BE SIGNED BY THE ENGINEER OF RECORD. |
| INITIALS ARE NOT ACCEPTIBLE. |
| FS 471.025 |
| |
| 2)NOTE: PLEASE SUBMIT ALL MANUFACTURE |
| CUT/SPEC SHEETS FOR ATS (S) TO BE |
| INSTALLED. |
| PLEASE SEE 225.36, THIS SHALL BE SERVICE |
| ENT RATED. PLEASE SEE GEN IS NOT PART OF |
| THIS PERMIT APPLICATION. PLEASE SEE |
| GROUPING OF DISCONNECTING MEANS WILL BE |
| REQUIRED WITH EXISTING MAINS ETC. |
| 225.34 |
| GEN IS TO BE SUBMITTED UNDER SEPARATE |
| PERMIT IF NOT IN THIS SCOPE OF WORK. |
| GEN WILL NOT BE PERMITTED AT LOCATION |
| /FLR AS SHOWN ON PLANS FOR FUTURE |
| PERMIT. |
| |
| 3)NOTE: PLEASE SEE ELECTRICAL ROOM DOES |
| NOT SEEM TO SHGOW MIN CLEARENCE REQUIRED |
| UNDER 110.26. |
| |
| 4)NOTE: PLEASE SHOW ALL CONTINUOUS LOADS |
| AT 125%. 215.3,230.42, ETC. |
| |
| 5)NOTE: PLEASE SHOW GROUNDING FOR |
| TRANSFORMER 250.30 |
| |
| PLEASE REMOVE ALL OLD/VOIDED SHEETS AND |
| ONLY INSERT NEW REVISED SHEETS INTO |
| COMPLETE SETS FOR REVIEW AND STAMPING. |
| ONE SET OF OLD/VOIDED SHEETS SHOULD BE |
| SUBMITTED FOR REFERENCE. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE DO NOT HESITATE TO CALL. |
| |