2005-06-28 00:00:00DENIED;
 PLEASE ADJUST YOUR NOTES, DETAILS OR
 SUBMITTALS TO REFLECT THE FOLLOWING
 INFORMATION REQUIRED FOR PLAN REVIEW.
 1.COMPLY WITH FBC-2001 SEC 424.2 PRIVATE
 SWIMING POOLS. (NOTES)
 2.FBC-2001 SEC. 424.2.6.1 ENGINEER
 DESIGN, CONSTRUCTION AND WORKMANSHIP.
 ANSI/NSPI-4 92 AND NSPI-5 (NOTES)
 3.FBC-2001 424.2.8.1 VALVES SHALL BE
 MADE OF MATERIALS THAT ARE APPROVED IN
 THE FLA. BLDG. CODE, PLUMBING. THEY WILL
 BE READILY ACCESSIBLE FOR MAINT. AND
 REMOVAL. SEC. 424.2.8.2 (NOTES)
 FILL WAY VALVES SHALL BE INSTALLED TO
 INSURE PROPER FUNCTION OF THE FILTRATION
 SYSTEM SEC. 424.2.8.3 WHERE CHECK VALVES
 ARE INSTALLED THEY SHALL BE OF THE SWING
 OR VERTICAL CHECK PATTERNS SEC.424.2.8.4
 4.FBC-2001 424.2.9 WATER SUPPLY LOCAL
 ORD.#2853-95 BACKFLOW REQUIRED ON WATER
 SEVICE. (NOTES)
 5.FBC-2001 424.2.12.1 PRESSURE TEST.
 PERR MANUFACTURE RECOMMENDATIONS NO AIR
 TEST SHALL BE SHALL BE APPROVED FOR PVC
 PIPE AND FITTINGS. (NOTES)
 6.FBC-2001 SEC.424.2.13.2 JOINTS AND
 FITTINGS FBC PLBG SEC 605.21, PURPLE
 PRIMER REQUIRED ON PVC PIPE-ING (NOTES)
 7.424.2.14.1 SWIMING POOL HEATERS SHALL
 BEAR THE LABLE OF A RECOGNIZEDTESTING
 AGENCY. 424.2.14.2 POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN BPUMP
 IS SHUT OFF. 424.2.14.4 ALL WATER HEATER
 SHALL BE INSTALLED WITH FLANGES OR
 UNIONS CONNECTIONS ADJACENT TO
 HEATERS.(NOTES)
 8.FBC.2001 424.2.15 GAS PIPING SHALL
 COMPY WITH FBC FUEL GAS. SEPARATE PLANS
 AND PERMIT REQUIRED. (NOTES)
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695
  
  