Plan Review Notes
Plan Review Notes For Permit 05060722
Permit Number 05060722
Review Stop G
Sequence Number 3
Notes
Date Text
2006-04-17 00:00:00******REVISION DENIED******
 REFERENCE: FBC-2004 FUEL GAS, AND CITY
 OF WEST PALM BEACH, AMENDMENTS TO
 FBC-2004, CHAPTER 1, ADMINISTRATION:
  
 THE FOLLOWING INFORMATION IS REQUIRED
 FOR PLAN REVIEW FOR THE GAS REVISION:
  
 1. PER CITY AMENDMENTS SECTION 106
 CONSTRUCTION DOCUMENTS: 106.1 SUBMITTAL
 DOCUMENTS. ALL INFORMATION, DRAWINGS,
 SPECIFICATIONS, AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNITURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 2. PER FBC 2004 FUEL GAS, INDICATE ON
 THE REVISION THE TYPE OF PIPING MATERIAL
 BEING USED.
 3. PLEASE CLARIFY DELIVERY PRESSURE, RE-
 VISION INDICATES 2.5 LB PSI. DELIVERY
 PRESSURE IS EITHER A 0.5 LB PSI OR A 2
 LB PSI SYSTEM. CLEARLY INDICATE ON THE
 DRAWING THE DELIVERY PRESSURE. NOTE: IF
 SYSTEM IS BEING REVISED TO A 2 LB PSI
 SYSTEM SUBMIT MANUFACTURE SHEETS FOR 2LB
 PSI REGULATORS, AND INDICATE THEIR
 LOCATION ON THE DRAWING PER FBC-2004
 FUEL GAS SEC. 402.2
 4. FUTURE GENERATOR INDICATED ON DRAWING
 NEEDS TO HAVE A SHUT OFF VALVE AND A
 HARD CAP (PRESSURE CAP) INDICATED ON
 DRAWING.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721