2006-04-17 00:00:00 | ******REVISION DENIED****** |
| REFERENCE: FBC-2004 FUEL GAS, AND CITY |
| OF WEST PALM BEACH, AMENDMENTS TO |
| FBC-2004, CHAPTER 1, ADMINISTRATION: |
| |
| THE FOLLOWING INFORMATION IS REQUIRED |
| FOR PLAN REVIEW FOR THE GAS REVISION: |
| |
| 1. PER CITY AMENDMENTS SECTION 106 |
| CONSTRUCTION DOCUMENTS: 106.1 SUBMITTAL |
| DOCUMENTS. ALL INFORMATION, DRAWINGS, |
| SPECIFICATIONS, AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNITURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| 2. PER FBC 2004 FUEL GAS, INDICATE ON |
| THE REVISION THE TYPE OF PIPING MATERIAL |
| BEING USED. |
| 3. PLEASE CLARIFY DELIVERY PRESSURE, RE- |
| VISION INDICATES 2.5 LB PSI. DELIVERY |
| PRESSURE IS EITHER A 0.5 LB PSI OR A 2 |
| LB PSI SYSTEM. CLEARLY INDICATE ON THE |
| DRAWING THE DELIVERY PRESSURE. NOTE: IF |
| SYSTEM IS BEING REVISED TO A 2 LB PSI |
| SYSTEM SUBMIT MANUFACTURE SHEETS FOR 2LB |
| PSI REGULATORS, AND INDICATE THEIR |
| LOCATION ON THE DRAWING PER FBC-2004 |
| FUEL GAS SEC. 402.2 |
| 4. FUTURE GENERATOR INDICATED ON DRAWING |
| NEEDS TO HAVE A SHUT OFF VALVE AND A |
| HARD CAP (PRESSURE CAP) INDICATED ON |
| DRAWING. |
| |
| END OF COMMENTS: |
| |