Plan Review Notes
Plan Review Notes For Permit 05060722
Permit Number 05060722
Review Stop G
Sequence Number 1
Notes
Date Text
2005-06-24 00:00:00DENIED
 GAS: PLAN REVIEW:FBC 2001 FUEL GAS
 FBC 2001 CHAPTER 1
  
 GENERATOR PERMITTING CHECKLIST
 (1 ) NO PERMIT PERTAINING TO A GENERATOR
 SHALL BE ISSUED UNTIL AN APPLICATION FOR
 THE GENERATOR IS APPLIED FOR.
 A REVIEW FOR THE GENERATOR IS REQUIRED.
 BUILDING,ELECTRIC,MECHANICAL, FUEL GAS,
 AND ZONING.
 THE BUILDING: REVIEW WILL BE FOR SLAB
 AND ANCHORING, FBC WIND LOADS 140 MPH.
 ELECTRICAL: RISER DRAWING, SIZE OF
 TRANSFERE SWITCH AND GENERATOR, SUBMIT
 MANFACTURES SPECIFICATION SHEETS.
 MECHANICAL: EXHAIST SYSTEM, CLEARANCES.
 FUEL GAS: GAS PERMIT APPLICATION
 REQUIRMENTS.
 ZONING: SITE SURVEY, SHOW LOCATION OF
 GENERATOR.
 (2) SECTION 104.2.1
 ALL INFORMATION, DRAWINGS
 SPECIFICATIONS AND ACCOMPANYING DATA
 SHALL BEAR THE NAME AND SIGNATURE OF THE
 PERSON RESPONSIBLE FOR THE DESIGN.
 (3)DISCRIPTION OF WORK ON THE
 APPLICATION: DESCRIBE PROJECT IN DETAIL.
 (3) SHOW THE TYPE OF PIPING MATERIAL
 BEING INSTALLED.
 (4)TYPE OF GAS ( L-P OR NATURAL)
 (5)SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMATION OF THE GAS
 VENTS PER.
 SEC 502 THRU 506.
 (6) SUBMIT MANFACTURE SHEETS FOR 2# PSI
 GAS REGULATORS, AND LOCATION.
 END OF COMMENTS, QUESTIONS CONTACT
 PAUL SCHMITZ 561-805-6692