2005-06-24 00:00:00 | DENIED |
| GAS: PLAN REVIEW:FBC 2001 FUEL GAS |
| FBC 2001 CHAPTER 1 |
| |
| GENERATOR PERMITTING CHECKLIST |
| (1 ) NO PERMIT PERTAINING TO A GENERATOR |
| SHALL BE ISSUED UNTIL AN APPLICATION FOR |
| THE GENERATOR IS APPLIED FOR. |
| A REVIEW FOR THE GENERATOR IS REQUIRED. |
| BUILDING,ELECTRIC,MECHANICAL, FUEL GAS, |
| AND ZONING. |
| THE BUILDING: REVIEW WILL BE FOR SLAB |
| AND ANCHORING, FBC WIND LOADS 140 MPH. |
| ELECTRICAL: RISER DRAWING, SIZE OF |
| TRANSFERE SWITCH AND GENERATOR, SUBMIT |
| MANFACTURES SPECIFICATION SHEETS. |
| MECHANICAL: EXHAIST SYSTEM, CLEARANCES. |
| FUEL GAS: GAS PERMIT APPLICATION |
| REQUIRMENTS. |
| ZONING: SITE SURVEY, SHOW LOCATION OF |
| GENERATOR. |
| (2) SECTION 104.2.1 |
| ALL INFORMATION, DRAWINGS |
| SPECIFICATIONS AND ACCOMPANYING DATA |
| SHALL BEAR THE NAME AND SIGNATURE OF THE |
| PERSON RESPONSIBLE FOR THE DESIGN. |
| (3)DISCRIPTION OF WORK ON THE |
| APPLICATION: DESCRIBE PROJECT IN DETAIL. |
| (3) SHOW THE TYPE OF PIPING MATERIAL |
| BEING INSTALLED. |
| (4)TYPE OF GAS ( L-P OR NATURAL) |
| (5)SUBMIT A DETAIL SHOWING THE TYPE, |
| LOCATION, SIZE AND TERMATION OF THE GAS |
| VENTS PER. |
| SEC 502 THRU 506. |
| (6) SUBMIT MANFACTURE SHEETS FOR 2# PSI |
| GAS REGULATORS, AND LOCATION. |
| END OF COMMENTS, QUESTIONS CONTACT |