Plan Review Notes
Plan Review Notes For Permit 05060716
Permit Number 05060716
Review Stop B
Sequence Number 2
Notes
Date Text
2005-07-25 00:00:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)CHANGES TO THE PLAN ARE TO BE
 CLOUDED AND, IF DONE IN INK, TO BE
 INITIALED BY THE ENGINEER.
  
 2.)THE WIND DESIGN CRITERIA
 FBC1606.1.7 IS TO BE A PART OF THE PLAN,
 NOT AN UNSIGNED AND UNSEALED SHEET.IT
 IS TO BE DONE BY THE ENGINEER.
  
 3.)THE TRUSS ENGINEERING AND TRUSS
 LAYOUT PREPARED BY HIRMET TUMAY, PE DO
 NOT HAVE A TITLE BLOCK FAC61G15-23.002.
  
 4.)THE TRUSS ENGINEERING HAS A STAMP
 INSTEAD OF A SIGNATURE.EACH SHEET IS
 TO BE SIGNED BY THE ENGINEER, NOT
 STAMPED.PLEASE CONTACT FBPE IF YOU ARE
 NOT IN AGREEMENT AND HAVE THEM EMAIL OR
 CALL ME.IN PRIOR CONVERSATIONS WITH
 FBPE THEY HAVE INSISTED ON A "WET
 SIGNATURE".
  
 5.)THE STANDARD GABLE END DETAIL,
 STGBL77 IS NOT SIGNED AND SEALED.
 INDICATE ON THAT SHEET THE WIND DESIGN
 CRITERIA AND THAT FBC2313.4.1 HAS BEEN
 MET.THIS IS BEING REQUESTED BECAUSE
 THE DETAIL DOES NOT INCLUDE BLOCKING AND
 ADDITIONAL BRACING SHOWN IN BCSI-B6
 PREPARED BY TPI AND WTCA.ALSO NOTE
 THAT THE SAMPLE PROVIDED WAS FOR 100MPH
 WIND ZONE, BUT HAD MORE BRACING.
  
 6.)HAVE THE TRUSS LAYOUT AND
 ENGINEERING REVIEWED BY ENGINEER OF
 RECORD FAC61G15-30.003(2).
  
 7.)SEE ATTACHED FS553.80(2)(B).A 4X
 PLAN REVIEW WILL BE CHARGED IF THE
 COMMENTS ARE NOT CORRECTLY ADDRESSED.
  
 8.)NEW COMMENT - THE APPLICATION
 STATES "WITH SCREEN".NO SCREEN IS
 SHOWN ON THE PLAN.EITHER INCORPORATE
 YOUR SCREEN STRUCTURAL DETAILS INTO YOUR
 PLAN OR REMOVE FROM THE APPLICATION.