Plan Review Notes For Permit 05060670 |
Permit Number |
05060670 |
|
Review Stop |
E |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2006-03-13 00:00:00 | *** UNSAT *** | | | | ** PLEASE SEE ITEMS BELOW HAVE REDLINED | | ON THE LAST TWO REVIEWS AND REVISIONS | | SUBMITTED, YET THESE ITEMS ARE STILL NOT | | BEING CORRECTED. | | | | 1)NOTE: PLEASE VERIFY OCP FOR CU, SHOWS | | 9.8KW, 40A OCP. PLEASE SEE MIN OCP | | REQUIRED TO BE SIZED PER 430 | | PLEASE ADJUST CONDUCTOR SIZE IF NEEDED. | | 240.4. 310.16 | | | | 2)NOTE: PLEASE SEE A MIN 8' GROUND ROD | | IS REQUIRED PER 250.52A5 | | | | 3)NOTE: PLEASE VERIFY MIN OCP FOR AHU#2, | | PER 424.3B, MIN OCP 125%. | | PLEASE ADJUST. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW. IF THERE ARE ANY QUESTIONS, | | PLEASE DO NOT HESITATE IN CONTACTING | | THIS OFFICE. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 561-805-6717 | | [email protected] |
|