2006-03-13 00:00:00*** UNSAT ***
  
 ** PLEASE SEE ITEMS BELOW HAVE REDLINED
 ON THE LAST TWO REVIEWS AND REVISIONS
 SUBMITTED, YET THESE ITEMS ARE STILL NOT
 BEING CORRECTED.
  
 1)NOTE: PLEASE VERIFY OCP FOR CU, SHOWS
 9.8KW, 40A OCP. PLEASE SEE MIN OCP
 REQUIRED TO BE SIZED PER 430
 PLEASE ADJUST CONDUCTOR SIZE IF NEEDED.
 240.4. 310.16
  
 2)NOTE: PLEASE SEE A MIN 8' GROUND ROD
 IS REQUIRED PER 250.52A5
  
 3)NOTE: PLEASE VERIFY MIN OCP FOR AHU#2,
 PER 424.3B, MIN OCP 125%.
 PLEASE ADJUST.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  