Plan Review Notes For Permit 05060670 |
Permit Number |
05060670 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-07-20 00:00:00 | BUILDING REVIEW CHECKLIST: | | 1- SHUTTERS UNDER A SEPARATE PERMIT. | | 2- NEED WORST CASE SCENARIO ENERGY CALCS | | 3- CLARIFY DOOR/WINDOW SCHEDULE. DON'T | | MIX TOGETHER DOOR/WINDOW SYMBOLS USED. | | 4- REVISE DETAIL 5/D1: CONNECTOR HTS20 | | CAN'T SUPPORT BEAM. | | 5- TRUSS ANCHOR SCHEDULE: UPDATE HUS26 | | NAIL SIZE. SEE LATEST CATALOGUE. | | 6- ROOF FRAMING PLAN: REVISE CONNECTOR | | SPECIFIED AT ENTRY PORCH TO MATCH | | DETAILS 5/D1 AND 6/D1. | | 7- RE-SUBMIT PRODUCT APPROVAL FOR: | | A) ROOF TILE. | | B) SINGLE HUNG WINDOWS. | | C) FIXED WINDOWS. | | 8- SHEET A-5 SHEAR VALUES NOTE: PROVIDE | | HAND CALCULATIONS. WHY USING TIMBER | | CONSTRUCTION MANUAL FOR TAPCONS VALUES? |
|