Plan Review Notes
Plan Review Notes For Permit 05060670
Permit Number 05060670
Review Stop B
Sequence Number 1
Notes
Date Text
2005-07-20 00:00:00BUILDING REVIEW CHECKLIST:
 1- SHUTTERS UNDER A SEPARATE PERMIT.
 2- NEED WORST CASE SCENARIO ENERGY CALCS
 3- CLARIFY DOOR/WINDOW SCHEDULE. DON'T
 MIX TOGETHER DOOR/WINDOW SYMBOLS USED.
 4- REVISE DETAIL 5/D1: CONNECTOR HTS20
 CAN'T SUPPORT BEAM.
 5- TRUSS ANCHOR SCHEDULE: UPDATE HUS26
 NAIL SIZE. SEE LATEST CATALOGUE.
 6- ROOF FRAMING PLAN: REVISE CONNECTOR
 SPECIFIED AT ENTRY PORCH TO MATCH
 DETAILS 5/D1 AND 6/D1.
 7- RE-SUBMIT PRODUCT APPROVAL FOR:
 A) ROOF TILE.
 B) SINGLE HUNG WINDOWS.
 C) FIXED WINDOWS.
 8- SHEET A-5 SHEAR VALUES NOTE: PROVIDE
 HAND CALCULATIONS. WHY USING TIMBER
 CONSTRUCTION MANUAL FOR TAPCONS VALUES?