Plan Review Notes
Plan Review Notes For Permit 05060666
Permit Number 05060666
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-17 00:00:00REDLINED,
  
  
 1)MISSING RECEPT 210.52
  
 2)PLANS SHOW BATH RM CIRCUITED AS #25,
 HOWEVER PANEL SCHEDULE SHOWS THIS AS
 COOKTOP.
  
 3)MIN OCP FOR AHU#2, 125% 424.3B
  