Plan Review Notes
Plan Review Notes For Permit 05060663
Permit Number 05060663
Review Stop E
Sequence Number 2
Notes
Date Text
2006-01-10 00:00:00********* UNSAT **********
  
  
 1)NOTE: PLEASE SEE PANEL "A" IS MISSING
 LOAD FROM PANEL "B"AND "C".
 PLEASE ALSO SEE LOADS ON PANEL "B" AND
 "C". SOME ARE SHOWN WITH 83 KW, 96, KW
 ETC.
 PLEASE ADJUST LOADS AND CALCUALTIONS.
 220, 215.5
  
 2)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52
  
 3)NOTE: PLEASE SEE SOME CIRCUITING SHOWN
 ON PLANS AND OTHERS NOT SHOWN. PLEASE
 SEE CIRCUIT A-38 ON PLANS AND BLANK ON
 SCHEDULE.
 EITHER SHOW ALL CIRCUITING AND CORRELATE
 WITH PANEL SCHEDULE OR DO NOT SHOW ANY
 CIRCUITING.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE IN CONTACTING
 THIS OFFICE.
  