2005-06-23 00:00:00 | DENIED | | REFERENCE: FBC-2001 PLUMBING | | FBC-2001 CHAPTER 1 | | | | 1. SUBMIT TWO SETS OF PLANS SHOWING THE | | LOCATION OF THE TRENCH DRAIN, THE OIL | | WATER SEPERATOR, THE PIPING AND THE | | LOCATION OF CONNECTION TO THE SEWER | | LINE. SHOW ALL PIPE SIZES, CLEANOUTS, | | VENTS ECT. SECTION 104.2.1. | | | | 2. SUBMIT A DWV RISER ISOMETRIC. SECTION | | 104.3.1.1. | | | | 3. OIL/WATER SEPERATOR SHALL BE SIZED BY | | RODNEY COMPO, ENVIRONMENTAL COMPLIANCE | | MANAGER. PLEASE CONTACH HIM BY PHONE | | (561) 822-2272, BY FAX (561) 659- 7458, | | OR BY E-MAIL [email protected]. SUBMIT THE | | DETERMINATION SHEET FROM MR. COMPO WITH | | THE PLANS WHEN SUBMITTING. WASTE ORD. # | | 2938-96. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 653-2692 | | E-MAIL [email protected] |
|