2005-09-16 00:00:00*** DENIDE ***
 1) RETURN TRANSFER DUCTS NEED TO BE
 1 1/2 TIMES LARGER THAN THE SUPPLY
 AIR DUCTS. 2001 FBC/M 601.4 .
 EXP. 7" SUPPLY AIR DUCT REQUIRES A 9"
 RETURN AIR TRANSFER DUCT WITH A 1"
 UNDERCUT DOOR, 8" SUPPLY AIR DUCT
 REQUIRES A 10" RETURN AIR TRANSFER DUCT
 WITH A 1" UNDERCUT DOOR.