Plan Review Notes For Permit 05060623 |
Permit Number |
05060623 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2005-09-16 00:00:00 | *** DENIDE *** | | 1) RETURN TRANSFER DUCTS NEED TO BE | | 1 1/2 TIMES LARGER THAN THE SUPPLY | | AIR DUCTS. 2001 FBC/M 601.4 . | | EXP. 7" SUPPLY AIR DUCT REQUIRES A 9" | | RETURN AIR TRANSFER DUCT WITH A 1" | | UNDERCUT DOOR, 8" SUPPLY AIR DUCT | | REQUIRES A 10" RETURN AIR TRANSFER DUCT | | WITH A 1" UNDERCUT DOOR. | | IF YOU HAVE ANY QUESTIONS PLEASE CALL | | TOM GORDON 805-6729 OR PATTY KRAUSS | | 805-6719. |
|