Plan Review Notes
Plan Review Notes For Permit 05060616
Permit Number 05060616
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-22 00:00:00 
 PLEASE INDICATE THE RATING AND OCP OF
 THE DISCONNECT AND SUB-PANEL FOR THE
 GENERATOR.
  
 SHOW THE LOCATION OF ALL EQUIPMENT ON A
 SITE PLAN.
  
 INDICATE THE PRIME MOVER IN THE SPEC OR
 ON THE DRAWING.
  
 THE FEEDERS ARE # 6 FROM A 100AMP
 GENERATOR. PLEASE SEE 445.13,
 310.15(B)(6) FOR CORRECT SIZING.
  
 CALL WITH ANY QUESTIONS.
  