Plan Review Notes
Plan Review Notes For Permit 05060615
Permit Number 05060615
Review Stop E
Sequence Number 1
Notes
Date Text
2005-06-27 00:00:00 
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} INDICATE THE PRIME MOVER FO RTHE
 GENERATOR.
  
 2} PLEASE PROVIDE A SITE PLAN INDICATING
 THE PHYSICAL LOCATION OF ALL SERVICE AND
 EMERGENCY EQUIPMENT.
  
 3} SUBMIT SPECIFICATIONS FOR THE
 TRANSFER SWITCH. INDICATE COMPLIANCE
 WITH 702.8
  
 4} SUBMIT LOAD CALCULATIONS FOR THE
 INTENDED CONNECTED EMERGENCY LOAD.
  
 5} THE PLAN SUBMITTED MUST BE SEALED BY
 THE ARCHITECT OF RECORD PER 481 FS.
 NOTE: THE CONTRACTOR MAY USE HIS OWN
 PLANS UNDER 481.229 FS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026
  
  
  