Plan Review Notes For Permit 05060615 |
Permit Number |
05060615 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2005-06-27 00:00:00 | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} INDICATE THE PRIME MOVER FO RTHE | | GENERATOR. | | | | 2} PLEASE PROVIDE A SITE PLAN INDICATING | | THE PHYSICAL LOCATION OF ALL SERVICE AND | | EMERGENCY EQUIPMENT. | | | | 3} SUBMIT SPECIFICATIONS FOR THE | | TRANSFER SWITCH. INDICATE COMPLIANCE | | WITH 702.8 | | | | 4} SUBMIT LOAD CALCULATIONS FOR THE | | INTENDED CONNECTED EMERGENCY LOAD. | | | | 5} THE PLAN SUBMITTED MUST BE SEALED BY | | THE ARCHITECT OF RECORD PER 481 FS. | | NOTE: THE CONTRACTOR MAY USE HIS OWN | | PLANS UNDER 481.229 FS. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | FAX/:561/659-8026 | | | | | | |
|