Plan Review Notes
Plan Review Notes For Permit 05060577
Permit Number 05060577
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2005-07-12 00:00:00******DENIED******
  
 1) PLEASE ILLUSTRATE THE ON SITE
 LOCATION OF THE GENERATOR AND FUEL
 SUPPLY.
  
 2) PLEASE NOTE THAT SEPARATE SHOP
 DRAWINGS AND PERMIT IS REQUIRED FOR FIRE
 PUMP INSTALLATION. AT THAT TIME, PLEASE
 PROVIDE CUT SHEETS AND FACTORY CURVE
 INFORMATION.
  
 3) IN ACCORDANCE WITH LOCAL REQIREMENTS,
 A NEW FIRE PUMP SERVING A HIGHRISE
 STRUCTURE SHALL BE A MINIMUM OF 1250
 GPM.
  
 4) PLEASE SHOW THE LOCATION OFEXHAUST
 IN REGARDS TO SURROUNDING AREA AND
 OPENINGS.
  
  
 MIKE WENNERGREN, A/CAPTAIN
 WPBFR(561) 805-6722 OR 835-2951