2005-06-29 00:00:00 | ********* UNSAT ************ |
| |
| 1)NOTE: PLEASE SEE FIRE PUMP AND FIRE |
| PUMP CONTROLLER WAS SUBMITTED WITH |
| GENERATOR/ATS PERMIT. |
| PLEASE SEE FIRE PUMP IS TO BE SUBMITTED |
| UNDER SEPARATE PERMIT . |
| PLEASE INCLUDE EXISTING RISER DIAGRAM |
| WITH THE FIRE PUMP PERMIT APPLICATION |
| PACKAGE. NOTE: RISER FOR EXISTING BLDG |
| REQUIRES PLANS TO BE SIGNED, DATED AND |
| SEALED BY ENGINEER OF RECORD. |
| PLEASE ALSO SUBMIT THREE SETSOF PLANS |
| AND SPECS AS THIS IS A THRESHOLD BLDG. |
| PLEASE SEE MECH/ FIRE REVIEW NOTES, FUEL |
| IS ALSO UNDER A SEAPARATE PERMIT. |
| 215.5, FBC 104.2.1 |
| |
| 2)NOTE: PLEASE PROVIDE RISER DIAGRAM FOR |
| INSTALLATION OF GEN, ATS. THREE SETS OF |
| SIGNED, SEALED PLANS, SPECS ETC FOR GEN |
| PERMIT. PLEASE BE SURE KW RATING OF GEN |
| SPECS CORRELATE WITH PLANS/RISER. |
| |
| *************************************** |
| PLEASE SEE THE ABOVE IS REQUIRED DUE TO |
| THIS INFORMATION NOT BEING SUBMITTED ON |
| ORIGINAL BLDG PLANS. A "PROVISO" |
| CONDITION WAS GIVEN IN ORDER TO ISSUE |
| THE BASE BLDG PERMIT. THE CONDITION |
| AGREED AND SET-FORTH WAS ALL OF THE |
| ABOVE WAS TO BE SUBMITTED UNDER SEPARATE |
| PERMITS, SEPARATE FEES ETC. |
| PLEASE SEE THIS APPLICATION IS ONLY FOR |
| INSTALLATION OF GEN AND ATS. |
| |
| *************************************** |
| |
| PLEASE SEE ANY POSSIBEL COMMENTS FROM |
| OTHER TRADES WHICH MAY AFFECT ELECTRICAL |
| PLANS. |
| |
| PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| REVIEW. IF THERE ARE ANY QUESTIONS, |
| PLEASE CALL. |
| |
| |