Plan Review Notes For Permit 05060508 |
Permit Number |
05060508 |
|
Review Stop |
B |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2005-06-10 00:00:00 | BUILDING PLAN REVIEW | | *******DENIED******* | | MYRON JACOBS(561) 805 6726 | | E-MAIL: [email protected] | | | | FBC = FLORIDA BUILDING CODE 2001 | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | F.S.= FLORIDA (STATE) STATUTE | | | | 1) FBC 1606.2.5THE SYSTEM SELECTED | | FROM THE SUBMITTED FLAT ROOF PRODUCT | | APPROVAL NOA HAS A MAXIMUM DESIGN | | PRESSURE OF LESS THAN -89 PSF AND CITES | | GENERAL LIMITATION #9 (SEE PAGE 23 OF | | 31).GENERAL LIMITATION #9 PROHIBITS | | RATIONAL ANALYSIS OR EXTRAPOLATION TO | | ENHANCE THE UPLIFT PRESSURE AT PERIMETER | | AND CORNER AREAS BY REDUCING THE | | FASTENER SPACING IN THESE AREAS.EITHER | | SELECT AN ALTERNATIVE SYSTEM (OR PRODUCT | | APPROVAL) THAT DOES NOT CITE GENERAL | | LIMITATION #9.ALTERNATIVELY IF THE | | SELECTED SYSTEM DOES CITE GENERAL | | LIMITATION #9, IT MUST HAVE A MAXIMUM | | DESIGN PRESSURE THAT EXCEEDS THE | | PRESSURE IN ROOF ZONE 3 (TYPICALLY -89 | | PSF FOR MEAN ROOF HEIGHT OF 30 FEET OR | | LESS). SEE PAGES 24-26 FROM THE REPORT | | FOR MORE INFORMATION. | | | | BUILDING PLAN REVIEW | | MYRON JACOBS | | TEL: (561)805-6726 | | FAX: (561)659-8026 | | [email protected] |
|